NSYTRV162-Terminal Block Schneider

Linergy TR Terminal Block Schneider is terminal block for Linergy. It belongs to linergy passthrough terminal block with 16 mm² nominal cross section. The rated operational voltage is 600V conforming to CSA/cURus, 1000V conforming to EN/IEC 60947-7-1 and 690V conforming to ATEX Exe II Ex II 2 GD. The rated current is 76A conforming to EN/IEC 60947-7-1, 85A conforming to CSA/cURus and 22A conforming to ATEX Exe II Ex II 2 GD. It has grey surface treatment. Mounting by clip-on and sideways connection by single-level 1×1 screw terminals. It could be connection and disconnection by screwdriver. It is compatible with spacial enclosures for Prisma G, Prisma P, Pragma, Prisma PH, Prisma Pack, Spacial, Kaedra, TeSys. Sold in lots of 50 units. Ambient air temperature for operation is from -40 to 130 °C conforming to IEC 60216-1 and VDE 0304-T21. Multi standards certified (ATEX, CSA, cURus, DNV, GL, LR, VDE, IEC-Ex, EAC). It is compliant with Green Premium (RoHS/REACH).

Contact us
Category:

Features

  • It belongs to linergy passthrough terminal block with 16 mm² nominal cross section
  • Mounting by clip-on and sideways connection by single-level 1×1 screw terminals
  • Releasing pressure on the sides stops the flow of cable ends
  • Facilitates storage by avoiding mixing cable ends of different sizes
  • Identifies the cross section of cable ends it contains

Specification

Main
Range Linergy
Product name Linergy TR
Product or component type Terminal block
device short name TRV
Accessory / separate part category Connection accessory
Terminal block type Passthrough
Terminal block level 1
Mounting mode Clip-on
Nominal cross section 16 mm²
Length 55.5 mm
Colour Grey
Quantity per set Set of 50
Complementary
Width 12.2 mm
Height 55 mm
Connections – terminals 1 x screw terminal: upstream (M5)
1 x screw terminal: downstream (M5)
number of connections 2
Connection position Sideways
Number of measurement input 2
Cable cross section 0.2…10 mm², flexible cable with cable end
0.2…16 mm², solid cable with cable end
1.5…25 mm², solid cable without cable end
1.5…25 mm², flexible cable without cable end
Tightening torque 2.5…3 N.m
Wire stripping length 14 mm
Tool type Connection: screwdriver
Disconnection: screwdriver
[Ue] rated operational voltage 1000 V conforming to EN/IEC 60947-7-1
600 V CSA
690 V conforming to ATEX Exe II Ex II 2 GD
600 V cURus
[In] rated current 76 A conforming to EN/IEC 60947-7-1
85 A cURus
85 A CSA
73 A conforming to ATEX Exe II Ex II 2 GD
Material Polyamide 6/6: insulating case
Copper alloy: connector and screw
Copper alloy: commoning link
Chromium-nickel steel: spring
Dielectric loss 0.01 at 1 MHz conforming to IEC 60250
0.01 at 1 MHz conforming to VDE 0303-T4
Dielectric constant 3.7 at 1 MHz
Resistivity 10000 MΩ.m conforming to IEC 60093
10000 MΩ.m conforming to VDE 0303-T30
Surface resistance 1000 GΩ conforming to IEC 60093
1000 GΩ conforming to VDE 0303-T30
Creep resistance 500 CTI (> 400 kB) conforming to IEC 60093
500 CTI (> 400 kB) conforming to VDE 0303-T30
Flame retardance V0, thickness0.8 mm conforming to UL 94
Product weight 30 g
Range compatibility Prisma G
Prisma P
Prisma PH
Prisma Pack
Spacial
Kaedra
Pragma
TeSys
Product compatibility Spacial enclosures
Environment
Product certifications DNV
VDE
IEC-Ex
LR
GL
cURus
CSA
EAC
ATEX
Dielectric strength 1000 V conforming to IEC 60243-1
Ambient air temperature for operation -40…130 °C conforming to IEC 60216-1
-40…130 °C conforming to VDE 0304-T21