Features
- Full switching of temperature signal
- Using photoelectric isolation technology
- RS485 communication interface
- Relay alarm output
- Low power consumption and low heat generation
- Support transmission output
- Smart appearance and high cost performance
- Transmission accuracy: 0.2%FS (20°C)
- I/O/power isolated from each other
Applications
- Detection, conversion and transmission of temperature in industrial automation control
- In the field of environmental monitoring, the measurement and transmission of atmospheric temperature, water temperature, ground temperature and other parameters are realized
- Used in weather stations, hydrological stations, geological exploration and other fields
- In the field of medical equipment, it realizes the monitoring and transmission of patient body temperature.
- Applied to the cold chain logistics industry to monitor and record the ambient temperature of logistics vehicles and cold storage
Specification
| Input | |
| Input signal | 2-wire/3-wire RTD, TC (Signal type and measuring range can be programmed via supporting PC software) |
| Output | |
| Output signal | 4-20mA、0-10mA、0-20mA、0-5V、1-5V |
| Output load | 4-20mA, 0-0mA, 0-20mA load resistance RL≤400Ω;
0-5V, 1-5V load resistance RL≥250KΩ |
| Power supply | |
| Power supply | DC20-32V |
| Power consumption | 1 in/1 out: ≤1W;
1 in/2 out, 2 in/2 out: ≤1.4W |
| Other parameters | |
| Insulation resistance (between input / output / power supply) | ≥100MΩ (500VDC) |
| Dielectric strength (between input / output / power supply) | 1500Vrms (1 min, no spark) |
| Operating temperature | -10~50 °C (no condensation, no freezing) |
| Relative humidity | 25%~85%RH |
| Storage temperature | -10~60 °C (no condensation, no freezing) |
| Temperature drift | 0.0075%FS/℃ |
| Mounting style | 35mmDIN rail mounting |
| Dimensions | 13*108*121.2mm (W * H * D) |
| Transmission accuracy (20 °C) | 0.2%FS±1 |
| Minimum resolution | 0.1℃ |
| Internal cold junction compensation temperature range | -10~50℃ |
| Cold junction compensation accuracy | ±1℃ |
| Response time | 50ms to reach 90% of the final value |
| Disconnection output | The user can configure through the PC software, and the disconnection output is optional between hold, maximum, and minimum
Hold: When the signal is disconnected or over range, the output will hold on as the output before the disconnection Maximum: When the signal is disconnected or over range, the output will be default 20.80mA Minimum: When the signal is disconnected or over range, the output will be default 3.00mA |
| Weight | Approximately 130 g |
| Electromagnetic compatibility | In line with GB / T18268 industrial equipment application requirements (IEC 61326-1) |
| Field devices applicable | 2-wire/3-wire RTD , TC sensor |





