Satec Multifunction Meter PM130

The Satec Multifunction Meter PM130 is a three-phase power meter. For basic power metering, the Satec PM130 series offers an affordable alternative to many analog meters used by utility, commercial, and industrial users.

Contact us

Feature of Satec Multifunction Meter

Multifunction Three-Phase Power Meter

  • For direct connection to the power line or via potential and current transformers, there are three voltage inputs and three current transformer-isolated AC inputs.
  • Volts, amps, power, power factor, neutral current, frequency, imbalanced voltage and current, and true RMS
  • Ampere/Volt demand meter with measurement capabilities at 25, 50, 60, and 400 Hz

Energy Meter for Billing/TOU

  • IEC 62053-22, Class 0.5S Four-quadrant polyphase static meter for both reactive and active energy
  • Active, reactive, and apparent energy counters; three-phase total and per-phase energy measurements
  • Eight tariffs, four totalization and tariff energy/demand registers, four seasons, four sorts of days, eight tariff adjustments each day, and a one-time, simple-to-programme tariff calendar schedule
  • Automatic daily profile log for total and tariff registers for energy and maximum demand

Instantaneous Waveform Recording

  • Real-time waveform monitoring in “scope mode”
  • Six-channel simultaneous one-cycle waveform recording at 64 samples per cycle

Din rail mounting or Panel mounting optional

Specification of Satec Multifunction Meter

Parameter Full Scale @ Input Range Accuracy Range
%

Reading

% FS Conditions
Voltage 120VxPT @ 120V

400VxPT @ 690V

0.2 0.02 10% to 120% FS 0 to 1,150,000 V

Starting voltage

1.5-5.0% FS (selectable)

Line current CT 0.2 0.02 For In = 5A

1% to 200% FS

For In = 1A

5% to 200% FS

0 to 50,000 A

Starting current 0.1% FS

Active power 0.36´PT´CT @ 120V

1.2´PT´CT @ 690V

0.3 0.02 |PF| ³ 0.51 -10,000,000 kW to

+10,000,000 kW

Reactive power 0.36´PT´CT@ 120V

1.2´PT´CT  @ 690V

0.3 0.04 |PF| £ 0.91 -10,000,000 kvar to

+10,000,000 kvar

Apparent power 0.36´PT´CT @ 120V

1.2´PT´CT @ 690V

0.3 0.02 |PF| ³ 0.51 0 to 10,000,000 kVA
Power factor 1.000 0.2 |PF| ³ 0.5, I ³ 2% FSI -0.999 to +1.000
Frequency 50 Hz

60 Hz

25 Hz

400 Hz

0.02

0.04

VL-N > 25V 15 Hz to 70 Hz

15 Hz to 70 Hz

15 Hz to 70 Hz

320 Hz to 480 Hz

Total Harmonic Distortion, THD V (I), %Vf (%If) 999.9 1.5 0.2 THD ³ 1%,

V ³ 10% FSV and

VL-N > 25V, I ³ 10% FSI

0 to 999.9
Total Demand Distortion, TDD,

%

100 1.5 TDD ³ 1%,

I ³ 10% FSI,

VL-N > 25V

0 to 100
Active energy Import & Export Class 0.5S under conditions as per IEC 62053-22:2003 0 to 999,999,999 kWh
Reactive energy Import & Export Class 0.5S under conditions as per IEC 62053-22:2003, |PF| £ 0.9 0 to 999,999,999 kvarh