Feature of Satec Multifunction Meter
Multifunction Three-Phase Power Meter
- For direct connection to the power line or via potential and current transformers, there are three voltage inputs and three current transformer-isolated AC inputs.
- Volts, amps, power, power factor, neutral current, frequency, imbalanced voltage and current, and true RMS
- Ampere/Volt demand meter with measurement capabilities at 25, 50, 60, and 400 Hz
Energy Meter for Billing/TOU
- IEC 62053-22, Class 0.5S Four-quadrant polyphase static meter for both reactive and active energy
- Active, reactive, and apparent energy counters; three-phase total and per-phase energy measurements
- Eight tariffs, four totalization and tariff energy/demand registers, four seasons, four sorts of days, eight tariff adjustments each day, and a one-time, simple-to-programme tariff calendar schedule
- Automatic daily profile log for total and tariff registers for energy and maximum demand
Instantaneous Waveform Recording
- Real-time waveform monitoring in “scope mode”
- Six-channel simultaneous one-cycle waveform recording at 64 samples per cycle
Din rail mounting or Panel mounting optional
Specification of Satec Multifunction Meter
Parameter | Full Scale @ Input Range | Accuracy | Range | ||
%
Reading |
% FS | Conditions | |||
Voltage | 120VxPT @ 120V
400VxPT @ 690V |
0.2 | 0.02 | 10% to 120% FS | 0 to 1,150,000 V
Starting voltage 1.5-5.0% FS (selectable) |
Line current | CT | 0.2 | 0.02 | For In = 5A
1% to 200% FS For In = 1A 5% to 200% FS |
0 to 50,000 A
Starting current 0.1% FS |
Active power | 0.36´PT´CT @ 120V
1.2´PT´CT @ 690V |
0.3 | 0.02 | |PF| ³ 0.51 | -10,000,000 kW to
+10,000,000 kW |
Reactive power | 0.36´PT´CT@ 120V
1.2´PT´CT @ 690V |
0.3 | 0.04 | |PF| £ 0.91 | -10,000,000 kvar to
+10,000,000 kvar |
Apparent power | 0.36´PT´CT @ 120V
1.2´PT´CT @ 690V |
0.3 | 0.02 | |PF| ³ 0.51 | 0 to 10,000,000 kVA |
Power factor | 1.000 | 0.2 | |PF| ³ 0.5, I ³ 2% FSI | -0.999 to +1.000 | |
Frequency | 50 Hz
60 Hz 25 Hz 400 Hz |
0.02
0.04 |
VL-N > 25V | 15 Hz to 70 Hz
15 Hz to 70 Hz 15 Hz to 70 Hz 320 Hz to 480 Hz |
|
Total Harmonic Distortion, THD V (I), %Vf (%If) | 999.9 | 1.5 | 0.2 | THD ³ 1%,
V ³ 10% FSV and VL-N > 25V, I ³ 10% FSI |
0 to 999.9 |
Total Demand Distortion, TDD,
% |
100 | 1.5 | TDD ³ 1%,
I ³ 10% FSI, VL-N > 25V |
0 to 100 | |
Active energy Import & Export | Class 0.5S under conditions as per IEC 62053-22:2003 | 0 to 999,999,999 kWh | |||
Reactive energy Import & Export | Class 0.5S under conditions as per IEC 62053-22:2003, |PF| £ 0.9 | 0 to 999,999,999 kvarh | |||
Apparent energy | Class 0.5S under conditions as per IEC 62053-22:2003 | 0 to 999,999,999 kVAh |