Features of QPV Frequency Transducer
- Accuracy of 0.5 class
- Supports a wide voltage range of 85~265VAC suitable for most countries
- Features four-channel output capability, accommodating up to 22 types of parameters for analog output
- Equipped with a front panel containing four keypads for configuring analog parameters, eliminating the need for additional configuration software
- Includes an RS-485 port for remote access to electrical data
- Achieves a rapid 500ms response time
- Designed for easy installation on a 35mm DIN rail
- Offers optional advanced electrical parameter readiness
- Provides an optional Sequence of Events (SOE) function
Application of QPV Frequency Transducer
- Panels for instrumentation
- Systems for control
- Panels for electrical distribution
- Generators and transmission systems
- Systems for SCADA
Specification of QPV Frequency Transducer
Signal Inputs | |
Input rating | 0-100V, 0-220V, 0-380V |
Overload | 1.2 times rated continuous; 5sec @ 10 times of rated current 1sec @ 2 times of rated voltage |
Burden | 0.5VA |
Measurement Output | |
Standard outputs | 4~20mA or 0~5V |
(others on request) | 0~20mA; |
5~10V; | |
0~10V; | |
Ripple | <0.5% peak to peak |
Load Resistance | Current output: 0<Lr<510Ω; |
Voltage output: Lr>10KΩ | |
Measurement Accuracy | |
Reference IEC 60688 | 0.5% or 0.2% @ F.S. |
Adjustment | Potentiometer “ZERO” and “SPAN” “T” types no need extra adjustment |
Frequency influence | <0.02% per Hz |
Load influence | <0.25% of F.S. for specific load range |
Auxiliary Supply | |
Rating | 85-265Vac/dc, Optional 12V, 24V, 48VDC |
Consumption | <3VA |
Galvanic isolation between I/O and AUX | |
Test voltage | 2KV RMS 50Hz for 1 minute |
impulse | 4KV 1.2/50µsec waveform |
Temperature requirements | |
Operating | -10~55C |
Storage | -40~70C, 20 ~ 93%RH; Noncondensing |