Specifications
range | VigiPacT |
---|---|
device short name | RH99M |
product or component type | Residual current protection relay |
relay application | Protection relay |
mounting support | DIN rail |
earth-leakage protection class | Type A |
type of setting | Selector |
residual earth-leakage sensitity adjustment type | Adjustable 9 settings |
Earth-leakage sensitivity | 0.03…30 A |
Earth-leakage time delay | Instantaneous for 0.03 A Adjustable 9 settings 0…4.5 s for 0.03…30 A |
Current sensors compatibility | TOA earth leakage current sensor A earth leakage current sensor L earth leakage current sensor |
[Ithe] conventional enclosed thermal current | 8 A |
minimum load | 10 mA at 12 V |
[Us] rated supply voltage | 220…240 V AC 50/60 Hz 55…110 % |
power consumption in VA | 4 VA |
Monitored distribution system | 1000 V – AC at 50/60 Hz (maximum) 1000 V – AC at 400 Hz (maximum) |
earthing system | TN-S TT IT |
[Uimp] rated impulse withstand voltage | 8 kV |
reset | Manual reset |