Features of S202M-C20UC ABB Miniature Circuit Breaker
- Outstanding Breaking Capacity: Demonstrates exceptional breaking capacity for reliable protection.
- Dual Connection Function: Equipped with a double connection function for lead wires and bus bars, enhancing flexibility.
- Efficient Stored Energy Operation: Utilizes stored energy operation for swift closing and extended service life.
- Easy Installation and Disassembly: Offers convenient installation and disassembly for user convenience.
- Clear Contact On-Off Indication: Provides a clear indication of contact status, enhancing security.
- Environmentally Friendly and Energy-Efficient: Prioritizes green environmental practices and energy conservation.
Specification of S202M-C20UC ABB Miniature Circuit Breaker
-
- Standards:
- IEC/EN 60898-2
IEC/EN 60947-2
-
- Tripping Characteristic:
- C
-
- Rated Operational Voltage:
- acc. to IEC 60898-1 400 V AC
acc. to IEC 60898-1 440 V DC
acc. to IEC 60898-2 400 V AC
acc. to IEC 60898-2 440 V DC
acc. to IEC 60947-2 440 V AC
acc. to IEC 60947-2 440 V DC
-
- Operational Voltage:
- Maximum (Incl. Tolerance) 440 V AC
Maximum (Incl. Tolerance) 500 V DC
Minimum 12 V AC
Minimum 12 V DC
-
- Rated Insulation Voltage (Ui):
- acc. to IEC/EN 60664-1 484 V
-
- Rated Impulse Withstand Voltage (Uimp):
- 4 kV
at 2000 m 5 kV
at Sea Level 6.2 kV
-
- Dielectric Test Voltage:
- 50/60 Hz, 1 min: 2 kV
-
- Input Voltage Type:
- AC/DC
-
- Rated Current (In):
- 20 A
-
- Rated Short-Circuit Capacity:
- (AC) 10 kA
(230 V AC) 10 kA
(253 V AC) 10 kA
(400 V AC) 10 kA
(440 V DC) 10 kA
-
- Rated Ultimate Short-Circuit Breaking Capacity (Icu):
- (220 V DC) 25 kA
(230 V AC) 15 kA
(400 V AC) 15 kA
(440 V AC) 10 kA
(440 V DC) 10 kA
-
- Rated Conditional Short-Circuit Current (Inc):
- (230 V) 15 kA
(400 V) 15 kA
-
- Rated Service Short-Circuit Breaking Capacity (Ics):
- (220 V DC) 20 kA
-
- Rated Frequency (f):
- 50 / 60 Hz
DC
-
- Power Loss:
- 4.52 W
at Rated Operating Conditions per Pole 2.26 W
-
- Power Supply Connection:
- Please Note Polarity of Device
-
- Contact Position Indication:
- Red ON / Green OFF
-
- Energy Limiting Class:
- 3
-
- Electrical Endurance:
- 20000 AC cycle
-
- Mechanical Endurance:
- 20000 cycle
-
- Number of Poles:
- 2
-
- Number of Protected Poles:
- 2
-
- Overvoltage Category:
- III
-
- Tightening Torque:
- 2.8 N·m
-
- Screw Terminal Type:
- Failsafe Bi-directional Cylinder-lift Terminal
-
- Actuator Marking:
- I / O
-
- Actuator Material:
- Insulation Group II, Black, Sealable
-
- Housing Material:
- Insulation Group I, RAL 7035
-
- Options Provided:
- Universal current
-
- Mounting on DIN Rail:
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
-
- Mounting Position:
- any
-
- Recommended Screw Driver:
- Pozidriv 2
-
- Accessories Available:
- Yes
-
- Remarks:
- Please note polarity of device
-
- Connecting Capacity:
- Busbar 10 / 10 mm²
Flexible with Ferrule 0.75 … 25 mm²
Flexible 0.75 … 25 mm²
Rigid 0.75 … 35 mm²
Stranded 0.75 … 35 mm²
-
- Installation Size:
- acc. to DIN 43880 1
-
- Terminal Type:
- Screw Terminals
Environmental
-
- Ambient Air Temperature:
- Operation -25 … +55 °C
Storage -40 … +70 °C
-
- Reference Ambient Air Temperature:
- 30 °C
-
- Degree of Protection:
- IP20
Enclosure with Cover IP40
-
- Pollution Degree:
- 3
-
- Environmental Conditions:
- 28 cycles
with 55 °C / 90-96 %
and 25 °C / 95-100 %
-
- Resistance to Vibrations acc. to IEC 60068-2-6:
- 5g, 20 cycles at 5 … 150 … 5 Hz with load 0.8 In
-
- Resistance to Shock acc. to IEC 60068-2-27:
- 25g / 2 shocks / 13 ms
-
- RoHS Status:
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
-
- Environmental Information:
- 2CDK400030D201
-
- SCIP:
- cec6beff-be12-4313-bcef-0d0cbaa3ae87 Germany (DE)
-
- REACH Declaration:
- 9AKK107492A1906