Features
- Reliable solution for power factor correction under severe operating conditions
- Especially suitable for higher voltage disturbances or in the presence of non-linear loads
- The rated current is larger to deal with the circulating current of harmonic current
- Provides a rated output power of 50 kVar at 400V AC, 50 Hz
- Fastened with ClampTite terminals
- Conforms to IEC 60831-1 and IEC 60831-2 standards
- Box product weight is 5.3 kg
Application
- Frequency converters
- Inverter based home appliances
- Solar inverters
- Variable speed motor drives
Specification
Range of product | PowerLogic |
---|---|
Product or component type | Heavy duty capacitor |
Network frequency | 50/60 Hz |
Series name | HDuty |
Network harmonic content | <= 20 % |
Electrical parameters | 45.1 kvar 380 V 50 Hz 50 kvar 400 V 50 Hz 53.8 kvar 415 V 50 Hz |
Maximum permissible voltage | 1.1 x Un (8 hours over 24 hours) |
continuous overcurrent capacity | 1.8 x In |
Rated voltage | 380…415 V AC 50/60 Hz |
Dielectric losses | < 0.2 W/kvar |
---|---|
Power losses | < 0.5 W/kVAr |
Capacitance tolerance | – 5 % to 10 % |
Voltage test | 2.15 x Un AC between terminals for 10 s <= 660 V – 3 kV AC between terminal and container for 10 s >= 660 V – 6 kV AC between terminal and container for 10 s |
Inrush current | 250 x In |
Maximum switching operation per year | 7000 |
Service life in hours | 130000 h |
Dielectric material | Metallized polypropylene film with Zn/Al alloy, special resistivity & profile, special edge (wave cut) |
Impregnation material | Non-PCB dry PUR resin Biodegradable |
Type of installation | Indoor installation |
Connections – terminals | Stud terminals |
Mounting mode | Upright/horizontal |
Diameter | 136 mm |
Height | 321 mm |
Product weight | 5.3 kg |
Standards | IEC 60831-2 IEC 60831-1 |
---|---|
IP degree of protection | IP00 |
Operating altitude | 2000 m |
Temperature class | D |
Ambient air temperature for operation | -25…55 °C |
Relative humidity | 95 % |
Warranty | 18 months |
---|