Feature
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage
- / Over temperature
- Cooling by free air convection
- Can be installed on DlN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment} approved
- BS EN/EN61000-6-2(BS EN/EN50082-2} industrial immunity level
- 100% full load burn-in test
- 2 years warranty
Application
- Industrial control system
- Mechanical and electrical equipment
- Electronic instruments
- Test and measurement instrument
- Laser related machine
- Charging related equipment
- Household appliances
- Power Sourcing Equipment of PoE
Specification
MODEL | EDR-120-12 | EDR-120-24 | EDR-120-48 | |
OUTPUT |
DC VOLTAGE | 12V | 24V | 48V |
RATED CURRENT | 10A | 5A | 2.5A | |
CURRENT RANGE | 0 ~ 10A | 0 ~ 5A | 0 ~ 2.5A | |
RATED POWER | 120W | 120W | 120W | |
RIPPLE & NOISE (max.) Note.2 | 100mVp-p | 120mVp-p | 150mVp-p | |
VOLTAGE ADJ. RANGE | 12 ~ 14V | 24 ~ 28V | 48 ~ 55V | |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load | |||
HOLD UP TIME (Typ.) | 16ms/230VAC 10ms/115VAC at full load | |||
INPUT |
VOLTAGE RANGE Note.6 | 90 ~ 264VAC 127 ~ 370VDC | [DC input operation possible by connecting AC/L(+), AC/N(-)] | |
FREQUENCY RANGE | 47 ~ 63Hz | |||
EFFICIENCY (Typ.) | 85% | 87.5% | 88.5% | |
AC CURRENT (Typ.) | 2.25A/115VAC 1.3A/230VAC | |||
INRUSH CURRENT (Typ.) | 20A/115VAC 35A/230VAC | |||
LEAKAGE CURRENT | <1mA / 240VAC | |||
PROTECTION |
OVERLOAD |
105 ~ 130% rated output power | ||
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||||
OVER VOLTAGE |
14 ~ 17V | 29 ~ 33V | 56 ~ 65V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||||
OVER TEMPERATURE | Shut down o/p voltage, re-power on to recover | |||
ENVIRONMENT |
WORKING TEMP. | -20 ~ +60℃ (Refer to “Derating Curve”) | ||
WORKING HUMIDITY | 20 ~ 95% RH non-condensing | |||
STORAGE TEMP., HUMIDITY | -40 ~ +85℃, 10 ~ 95% RH | |||
TEMP. COEFFICIENT | ±0.03%/℃ (0 ~ 50℃) | |||
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||
SAFETY & EMC (Note 4) |
SAFETY STANDARDS | UL508,TUV BS EN/EN62368-1,EAC TP TC 004,BSMI CNS14336-1,IS13252(Part1)/IEC60950-1 approved;(meet BS EN/EN60204-1) | ||
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC | |||
ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH | |||
EMC EMISSION | Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class A | |||
EMC IMMUNITY |
Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),
heavy industry level, criteria A, EAC TP TC 020 |
|||
OTHERS |
MTBF | 2718.3K hrs min. Telcordia SR-332 (Bellcore) ; 474.7K hrs min. MIL-HDBK-217F (25℃) | ||
DIMENSION | 40*125.2*113.5mm (W*H*D) | |||
PACKING | 0.6Kg; 20pcs/13Kg/1.16CUFT | |||
NOTE |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5. lnstallation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. ln case the adjacent device is a heat source, 15mm clearance is recommended. 6. Derating may be needed under low input voltage. Please check the derating curve for more details. 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft}. |