Feature:
1. LED indication for On / Fault status
2. Protection for Input and output over /under voltage, over temperature, and short circuit
3. “Hot plug-in” design with back plane connection
4. High power density, RS485 Interface for Remote Adjusting, Controlling, Measuring and Signaling.
5. High Efficiency with low EMI. CE Safety and EMC certification
Applications
1. Power supply for all medium to high power DC loads
2. Telecommunication.
3. Rectifiers in DC systems with battery backup
4. Industrial control systems.
5. Charging and buffering of stationary batteries in electrical power plants
Specification
Input
Type | 220V/10A | 110V/20A |
Model No. | SET-220V/10A | SET-110V/20A |
Input voltage | 85-290VAC (Nominal 180-290VAC) | |
Input current | 13.6A | |
Input frequency range | 45 Hz-65 Hz | |
Power Factor | ≥ 0.99 at P nom ≥ 75% |
Output
Nominal output voltage (Vnom) | 220VDC | 110VDC |
Adjustable output voltage range | 190-300VDC | 95-150VDC |
Voltage Stabilization Accuracy | ± 0.5% | |
Current Stabilization Accuracy | ± 1 % | |
Nominal output current (Inom) | 10ADC@300VDC | 20A DC@150VDC |
Efficiency | ≥ 95 % | |
Charge characteristic line | IU Characteristic according to | |
DIN41772/DIN41773 | ||
Default value of the charging | 240V | 120V |
voltage | ||
O/p Overvoltage Vo> (factory | 302V | 151V |
set) | ||
Voltage ripple | ≤ 200 mV | |
Dynamic accuracy of the | <3% of Venom at load change | |
charging voltage | from 10% -90%-10% ;Transient | |
time<50 ms | ||
Short circuit protection | 15% – 30% of Inom when in short | |
circuit | ||
Parallel operation | Yes .Current Sharing ± 3% |
110V or 220V DC Rectifier System Mechanical
Type | 220V/10A | 110V/20A |
Model No. | SET-220V/10A | SET-110V/20A |
Weight approx. | 2.4 kgs | |
Dimensions (W/H/D) | 103x88x261 | |
Type of enclosure / | IP 20 | |
Protection class | ||
Color (front panel) | Front Black |
110V or 220V DC Rectifier System Technial Data
Communications interface | RS 485 |
Ambient temperature | Operation: -20° to+55° C , |
Storage:-40° to +70° C | |
Humidity | ≤ 90 % RH |
Cooling | Fan Cooled |
Climatic conditions | IEC-68-2-2, IEC-68-2-3, IEC-68-2-6 |
Max. Installation altitude | ≤2000 m |
Audible noise | < 50 db |
Connections | AC Input DC Output and Signalization at rear |
CE conformity | Yes |
Compliance to EMC standards | EN61000-4-2, EN-61000-4-6, EN-61000-4-3, EN-61000-4-12 |
Air Pressure | 70-106 Pa |
Insulation Resistance | Input Chassis & Output > 10M Ohms at 500VDC |
Dielectric strength | 2000V between Input, Output & Chassis for 1Min. |