SIMOCODE pro 3UF7 motor management and control devices

SIMOCODE pro 3UF7 is a flexible and modular motor management system for motors with constant speeds in the low-voltage performance range. It optimizes the connection between I&C and motor feeder, increases plant availability, and allows significant savings to be made for startup, operation, and preventive maintenance of a system.

Contact us
Category:

Feature of SIMOCODE pro 3UF7

  • Inverse-time delayed electronic overload protection (CLASS 5E to 40E)
  • Thermistor motor protection
  • Phase failure/asymmetry protection
  • Stall protection
  • Monitoring of adjustable limit values for the motor’s current
  • Voltage and power monitoring
  • Monitoring of the power factor φ (motor idling/load shedding)
  • Ground-fault monitoring
  • Temperature monitoring, e.g. via Pt100/Pt1000
  • Monitoring of operating hours, downtime number of starts, etc.

 

Application of SIMOCODE pro 3UF7

SIMOCODE pro is often used for automated processes where plant downtimes are very expensive (e.g. chemical, oil/gas, water/wastewater, steel or cement industries) and where it is important to prevent them using detailed operational, service and diagnostics data and to localize faults very quickly when they occur.

SIMOCODE pro is modular and space-saving and suited especially for operation in motor control centers (MCCs) in the process industry and for power plant technology.

  • Protection and control of motors in hazardous areas for types of protection EEx e/d according to ATEX Directive 2014/34/EU
    • With heavy starting (paper, cement, metal, and water industries)
    • In high-availability plants (chemical, oil, raw material processing industries, power plants)
  • Dry-running protection of centrifugal pumps based on active power monitoring for the type of protection Ex b

 

Specification of SIMOCODE pro 3UF7

Electromagnetic compatibility
EMC emitted interference according to IEC 60947-1 class A
EMC immunity according to IEC 60947-1 corresponds to the degree of severity 3
conducted interference
due to burst according to IEC 61000-4-4 2 kV (power ports) / 1 kV (signal ports)
due to conductor-earth surge according to IEC 61000-4-5 2 kV
due to conductor-conductor surge according to IEC 61000-4-5 1 kV
due to high-frequency radiation according to IEC 61000-4-6 10 V
field-based interference according to IEC 61000-4-3 10 V/m
electrostatic discharge according to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge
conducted HF interference emissions according to CISPR11 corresponds to the degree of severity A
field-bound HF interference emission according to CISPR11 corresponds to the degree of severity A
Inputs/ Outputs
product function
parameterizable inputs Yes
parameterizable outputs Yes
number of inputs 4
for thermistor connection 1
number of digital inputs with a common reference potential 4
digital input version
 type 1 acc. to IEC 61131 Yes
input voltage at digital input at DC-rated value 24 V
number of outputs 2
number of semiconductor outputs 0
number of outputs as a contact-affected switching element 2
switching behavior monostable
type of relay outputs Monostable
wire length for digital signals maximum 300 m
wire length for thermistor connection
with conductor cross-section = 0.5 mm² maximum 50 m
with conductor cross-section = 1.5 mm² maximum 150 m
with conductor cross-section = 2.5 mm² maximum 250 m
Protective and monitoring functions
product function
asymmetry detection Yes
blocking current evaluation Yes
power factor monitoring No
ground fault detection Yes
phase failure detection Yes
phase sequence recognition No
voltage detection No
monitoring of number of start operations Yes
overvoltage detection No
overcurrent detection 1 phase Yes
undervoltage detection No
undercurrent detection 1 phase Yes
active power monitoring No
product function
current detection Yes
overload protection Yes
evaluation of thermistor motor protection Yes
total cold resistance number of sensors in series maximum 1.5 kΩ
response value of thermoresistor 3 400 … 3 800 Ω
of the short-circuit control 9 Ω
release value of thermoresistor 1 500 … 1 650 Ω
Motor control functions
product function
parameterizable overload relay Yes
circuit breaker control Yes
direct start Yes
reverse starting Yes
star-delta circuit Yes
star-delta reversing circuit No
Dahlander circuit No
Dahlander reversing circuit No
pole-changing switch circuit No
pole-changing switch reversing circuit No
slide control No
valve control No
Communication/ Protocol
protocol is supported
PROFIBUS DP protocol Yes
PROFINET IO protocol No
PROFIsafe protocol No
Modbus RTU No
EtherNet/IP No
OPC UA Server No
LLDP No
Address Resolution Protocol (ARP) No
SNMP No
HTTPS No
NTP No
Media Redundancy Protocol (MRP) No
number of interfaces
according to PROFINET 0
according to PROFIBUS 1
according to Ethernet/IP 0
product function
web server No
shared device No
at the Ethernet interface Autocrossover No
at the Ethernet interface Autonegotiation No
at the Ethernet interface Autosensing No
is supported Device Level Ring (DLR) No
is supported by PROFINET system redundancy (S2) No
supports PROFIenergy measured values No
supports PROFIenergy shutdown No
transfer rate maximum 1.5 Mbit/s
identification & maintenance function
I&M0 – device-specific information Yes
I&M1 – higher level designation/location designation Yes
I&M2 – installation date Yes
I&M3 – comment Yes
type of electrical connection of the communication interface Screw-type terminal (1.5 Mbit)
Installation/ mounting/ dimensions
mounting position any
fastening method screw and snap-on mounting
height 100 mm
width 22.5 mm
depth 124.5 mm
required spacing
top 40 mm
bottom 40 mm
left 0 mm
right 0 mm
Connections/ Terminals
product component removable terminal for auxiliary and control circuit Yes
type of connectable conductor cross-sections
solid 1x (0.5 … 2.5 mm²), 2x ( 0.5 … 1.5 mm²)
finely stranded with core end processing 1x (0.5 … 2.5 mm²), 2x (0.5 … 1 mm²)
for AWG cables solid 1x (20 … 14), 2x (20 … 16)
tightening torque with screw-type terminals 0.6 … 0.8 N·m
tightening torque [lbf·in] with screw-type terminals 5.2 … 7 lbf·in
type of connectable conductor cross-sections for PROFIBUS wire 2x 0.34 mm², AWG 22
Ambient conditions
installation altitude at height above sea level
1 maximum 2 000 m
2 maximum 3 000 m; max. +50 °C (no protective separation)
3 maximum 4 000 m; max. +40 °C (no protective separation)
ambient temperature
during operation -25 … +50 °C
during storage -40 … +80 °C
during transport -40 … +80 °C
environmental category
during operation according to IEC 60721 3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
during storage according to IEC 60721 1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4
during transport according to IEC 60721 2K2, 2C1, 2S1, 2M2
relative humidity
during operation 10 … 95 %
contact rating of auxiliary contacts according to UL B300 / R300
Short-circuit protection
design of short-circuit protection per output Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A)
Electrical Safety
touch protection against electrical shock finger-safe
ATEX
certificate of suitability
acc. to Equipment and Protective System Intended for Use in Potentially Explosive Atmospheres Regulations 2016 (S.I. 2016 No.1107) ITS21UKEX0464, ITS21UKEX0455X
Galvanic isolation
(electrically) protective separation according to IEC 60947-1 All circuits with protective separation (double creepage paths and clearances), the information in the “Protective Separation” test report, No. A0258, must be observed (link see further information)
Control circuit/ Control
product function soft starter control Yes
type of voltage of the control supply voltage AC/DC
control supply voltage at AC
at 50 Hz rated value 110 … 240 V
at 60 Hz rated value 110 … 240 V
control supply voltage frequency
1 rated value 50 Hz
2 rated value 60 Hz
relative symmetrical tolerance of the control supply voltage frequency 5 %
control supply voltage at DC rated value
110 … 240 V
operating range factor control supply voltage rated value at DC
initial value 0.85
full-scale value 1.1
operating range factor control supply voltage rated value at AC at 50 Hz
initial value 0.85
full-scale value 1.1
operating range factor control supply voltage rated value at AC at 60 Hz
initial value 0.85
full-scale value 1.1
inrush current peak
at 240 V 10 A
duration of inrush current peak
at 240 V 1 ms