Features
- SmartLine platform features including SmartLine Connection Advantage when used with Experian
- Single input supporting up to 4-wire RTD sensor connection
- Dual input option supporting up to two (2) 3-wire RTD sensor connections
- Digital accuracy up to 0.15°C for RTD
- Callendar-Van Dusen sensor constants input
- HART7 communications
- DE communications
- Field housing, head mount, panel mount and DIN rail mounting options
- Transmitter and sensor diagnostics
- FM / CSA / ATEX / IEC Ex approvals
- Full compliance with SIL 2 / 3 requirement
- Up to a 4-year warranty
Applications
- Detection, conversion and transmission of temperature in industrial automation control
- In the field of environmental monitoring, the measurement and transmission of atmospheric temperature, water temperature, ground temperature and other parameters are realized
- Used in weather stations, hydrological stations, geological exploration and other fields
- In the field of medical equipment, it realizes the monitoring and transmission of patient body temperature.
- Applied to the cold chain logistics industry to monitor and record the ambient temperature of logistics vehicles and cold storage
Specification
Parameter | Description |
Input Span Adjustment Range | No limits to adjustments within the maximum range except minimum span limit of 1
engineering unit |
Analog Output
Digital Communications: |
Two-wire, 4 to 20 mA HART 7 protocol compliant
Honeywell Digitally Enhanced (DE) protocol compliant |
Output Failure Modes | Honeywell Standard: NAMUR NE 43 Compliance:
Normal Limits: 3.8 – 20.8 mA 3.8 – 20.5 mA Failure Mode: ≤ 3.6 mA and ≥ 21.5 mA ≤ 3.6 mA and ≥ 21.5 mA |
Output Accuracy | ±0.025 % span |
Supply Voltage Effect | 0.005 % span per volt. |
Transmitter Turn on Time (includes power up & test
algorithms) |
HART or DE: 6 sec. |
Analog Input | Stability: 0.05% of URL per year for 10 years
Maximum Lead Wire Resistance: Thermocouples and millivolts: 25 ohms/leg RTD and ohms: 25 ohms/leg |
Response Time
(delay + time constant) |
Analog Output
500 mSec to reach 96% of final value with 0 seconds damping |
Update time | 500 mSec for Single Input Units 1 Sec for Dual Input Units |
Damping Time Constant | HART: Adjustable from 0 to 102 seconds in 0.1 increments. Default: 0.50 seconds
DE: Discrete values 0.0, 0.3, 0.7, 1.5, 3.1, 6.3, 12.7, 25.5, 51.1, 102.3 seconds. Default: 0.3 seconds |
Ambient Temperature Effect | Digital Accuracy
For all RTD (except Pt200) and 500 ohm Input Types: 0.017 ohms/°C For RTD Pt200 and 2000 ohm Input Types: 0.034 ohms/C. Output D/A: 0.0045 % of span/°C |
Cold Junction Accuracy | ±0.5 °C |
Total Reference Accuracy | Digital Mode
Digital Accuracy + C/J Accuracy (T/C input types only) Analog Mode (HART only) Digital Accuracy + Output D/A Accuracy + C/J Accuracy (T/C input types only) Example: Transmitter in Analog Mode with Pt100 sensor and 0 to 200°C range Total Reference Accuracy = 0.15 °C + (200 °C / 100%) * 0.025% = 0.20 °C |
Sensor Burnout | Burnout detection is user selectable. Upscale or down scale with critical status. |
Vibration Effect | Per IEC60770-1 field or pipeline, high vibration level (10-2000Hz: 0.21 displacement/3g max acceleration) |
Electromagnetic Compatibility | IEC 61326-3-1 |
Isolation | 2000 VDC (1400Vrms) Galvanic isolation between inputs and output. |