TraceTek TTSIM series Water Leak Detection System

TraceTek TTSIM series water Leak detection system is a water leak detection module or sensor interface module that offers timely alerts for water leakage or presence in Data Centers, Server rooms, or Critical rooms. It is used with water leak sensing cables, and supports cable lengths up to 5,000 feet (1,500 meters).

Contact us

Feature of TraceTek TTSIM series water leak detection system

  • Voltage-free contacts for alarm signaling
  • Digitally displays the location of the liquid leak
  • LEDs indicate power, leakage, cable fault, and communication status.
  • Suitable for 24, 12,0, or 230 Vac 50/60 Hz or 12 or 24 Vdc power supplies.
  • Each unit has a unique address assigned by software – no switches are required.
  • Connects directly to BMS, PLC, and building control systems.
  • Connects directly to solenoid valves, pumps, and external remote alarm devices
  • Relay software is selectable for normally energized or normally de-energized operation.
  • DIN rail mount for easy installation, standalone indoor or outdoor installation.
  • Respond to a wide range of communication protocols with automatic protocol selection (MODBUS, Opto 22, and Metasys).
  • Monitors up to 150 meters of sensing cable, 10 different zones, and 10 individual sensors (probe, optical, floating, or submersible).

Specification of TTSIM water leak detection system

Models TTSIM-1A Leak Detection TTSIM-1 Leak Detection TTSIM-2 Leak Detection
Operating voltage 22 to 26 Vac, 3 W
12 Vdc +/– 10%, 2 W92 to 132 Vac, 3 W
24 Vdc +/– 10%, 2 W216 to 253 Vac, 3 W
22 to 26 Vac, 3 W
12 Vdc +/– 10%, 2 W
24 Vdc +/– 10%, 2 W
22 to 26 Vac, 3 W
12 Vdc +/– 10%, 2 W92 to 132 Vac, 3 W
24 Vdc +/– 10%, 2 W216 to 253 Vac, 3 W
Operating temperature 0°C to 50°C
Operating humidity 5% to 95% non-condensing
Communication protocol Modbus®, OptoMux™ or Johnson Controls Metasys™
Network configuration  RS-485 two-wire network, 9600 baud, addressable from 1 to 127
Maximum length of sensing cable 1500 m (5000 ft) 150 m (5000 ft)
Precision 0.5% of sensor length ± 0.6 m (2 ft) 0.1% of sensor length 0.5% of sensor length ± 0.6 m (2 ft)
Dimension 86 x 70 x 58 mm

Dimension of TraceTek TTSIM interface sensor module

dimension of TraceTek TTSIM water detection system

Application of TraceTek TTSIM interface sensor module

The water leak detection systems can be used in various applications such as piping and storage tank leaks.

Piping Detection Storage Tanks Detection
  1. Aboveground and underground pipelines for transmission and transfer.
  2. Piping within commercial buildings, control rooms, and airport tunnels.
  3. Cables within double-wall pipes.
  4. Leak detection for buried valves.
  5. Detection of leaks at mixers, flanges, valves, and pipework.
  1. Tank farms: Including tank bottoms, roofs, and general leaks.
  2. Detection of overfills and undetected leaks of unleaded gasoline.
  3. Early detection of fuel leaks and spills.
  4. Addressing roof drain and tank drain failures, and fractured tanks.