Feature
- AC or DC coil
- Lockable test button option and mechanical indicator as standard
- Variant with LED and integrated protection circuit
- Sockets Series 94 for printed circuit board, solder or for 35mm rail mount (EN 60715) with push-in, screw or screwless terminals
- 99 Series coil indication and EMC suppression modules and Type 86.30 timer modules
- Adaptors for alternative mount available
- UL Listing (relay/socket/jumper link)
- Cadmium-free contacts
- Contact material options
- European patent
Specification
Contact specification | ||||
Contact configuration | 2 CO (DPDT) | 3 CO (3PDT) | 4 CO (4PDT) | |
Rated current/Maximum peak current A | 10/20 | 10/20 | 7/15 | |
Rated voltage/
Maximum switching voltage V AC |
250/400 |
250/400 |
250/250 |
|
Rated load AC1 VA | 2500 | 2500 | 1750 | |
Rated load AC15 (230 V AC) VA | 500 | 500 | 350 | |
Single phase motor rating (230 V AC) kW | 0.37 | 0.37 | 0.125 | |
Breaking capacity DC1: 24/110/220 V A | 10/0.5/0.25 | 10/0.5/0.25 | 7/0.5/0.25 | |
Minimum switching load mW (V/mA) | 300 (5/5) | 300 (5/5) | 300 (5/5) | |
Standard contact material Coil specification Nominal voltage (UN) |
V AC (50/60 Hz) |
AgNi | AgNi | AgNi |
6 – 12 – 24 – 48 – 60 – 110 – 120 – 230 – 240 | ||||
V DC | 6 – 12 – 24 – 48 – 60 – 110 -125 – 220 | |||
Rated power AC/DC VA (50 Hz)/W | 1.5/1 | 1.5/1 | 1.5/1 | |
Operating range | AC | (0.8…1.1)UN | (0.8…1.1)UN | (0.8…1.1)UN |
DC | (0.8…1.1)UN | (0.8…1.1)UN | (0.8…1.1)UN | |
Holding voltage AC/DC | 0.8 UN / 0.5 UN | 0.8 UN / 0.5 UN | 0.8 UN / 0.5 UN | |
Must drop-out voltage AC/DC
Technical data Mechanical life AC/DC cycles |
0.2 UN / 0.1 UN
20 · 106 / 50 · 106 |
0.2 UN / 0.1 UN
20 · 106 / 50 · 106 |
0.2 UN / 0.1 UN
20 · 106 / 50 · 106 |
|
Electrical life at rated load AC1 cycles | 200 · 103 | 200 · 103 | 150 · 103 | |
Operate/release time ms | 10/5 | 9/5 | 9/5 | |
Insulation between coil
and contacts (1.2/50 μs) kV |
4 |
4 |
4 |
|
Dielectric strength
between open contacts V AC |
1000 |
1000 |
1000 |
|
Ambient temperature range °C | –40…+85 | –40…+85 | –40…+85 | |
Environmental protection | RT I | RT I | RT I |