Applications of ZHRV2-36G Voltage control relay
Used in air conditioning units, elevator machine rooms, pumps, fans, and other motor control applications, as protection of over-voltage, under voltage, phase failure, phase sequence and phase unbalance. When the power supply is abnormal, turn off the power supply to protect the equipment.
Features of ZHRV2-36G Voltage control relay
Built-in microprocessor, true RMS measurement, measurement accuracy ≤1%.knob setting, LED indicator showing working status.Use(magnetic latching)relay to achieve products low-power. DIN rail mounting.
Specification of ZHRV2-36G Voltage control relay
Rated supply voltage | AC 220V | ||
Rated supply frequency | 50/60Hz | ||
Contact Configuration capacity(A) | 32A.40A、63A、 80A Resistive | ||
Maximum load power | 7kVA(40A)、13kVA(63A). 17kVA(80A) | ||
Over-voltage action value | 36G:265V 36T:225~265V(Knob setting) | ||
Over- voltage reset value | 36G:257V 36T*(97%) Over voltage action value*(97%) | ||
Under-voltage action value | 36G:175V 36T:165~215V(Knob setting) | ||
Under-voltage reset value | 36G:180V 36T: *(103%) Under voltage action value*(103%) | ||
Action delay | 36G:0.1s 36T:0.1s~ 10s(Knob setting) | ||
Power on delay | 36G:2s 36T:0.3s~ 30s(Knob setting) | ||
Reset delay | 36G:1s 36T:0.3s~ 30s(Knob setting) | ||
Voltage measurement error | ≤1% | ||
Delay error | ±10%+0.1s | ||
Knob setting accuracy | ±1V | ||
Rated insulation voltage | 415V | ||
IP Class | IP 20 | ||
Class of pllution | Ⅲ | ||
Electrical Life | 105 | ||
Mechanical life | 106 | ||
Altitude | ≤2000m | ||
Allowable relative humidity | ≤50% ( 40°C ) (No condensation ) | ||
DIN rail Standard | width 35mm(IEC/EN60715) |