Features of SEL Arc Flash Relay
- Rapid Detection and Response: Detects arc-flash hazards within 2 milliseconds and initiates a trip signal to the circuit breaker.
- Minimized Equipment Damage: Reduces equipment damage during arc-flash events, improving system availability.
- Coordinated Protection: Integrates with upstream protection systems using SEL Mirrored Bits or IEC 61850 GOOSE messaging to ensure coordinated fault clearing.
- Versatile Installation: Suitable for both new and existing installations, including retrofitting SEL-751 relays.
- Robust Communication: Supports multiple communication protocols, including Ethernet-based protocols like Modbus TCP, DNP3, and IEC 61850.
- Reliable and Durable: Designed to operate in harsh environments with a wide temperature range and backed by a 10-year warranty.
- Arc-Flash Mitigation: detect arc flash by the combined light and high-speed overcurrent detection
Specification of SEL Arc Flash Relay
Basic parameters | |
Rated working voltage | DC24V |
AC current | 5A or 1A (specify when ordering) |
Frequency | 50HZ |
Working power consumption | Working normally, ≤ 3W
Protection operates, ≤ 6W |
AC current loop consumption | < 1VA/phase (IN =5A);
< 0.5VA/phase (IN =1A); |
Current working range | 0.08In~10In |
Time working range | 0~99s |
Setting accuracy | ≤±5%; |
Time accuracy | <±1%*setting time+20ms |
The whole group action time | Single criterion ≤ 7ms
Double criterion ≤ 20ms |
Arc signal input | |
Input type | Passive optical signal |
Input quantity | 3 |
Interface type: | Optical fiber |
Output contact capacity | |
A) Export relay: (3 routes) | |
Contact rated current carrying capacity | 250Vac/220Vdc, 5A |
Output type | Passive (NO/NC) |
B) Signal relay: (1 way) | |
Contact rated current carrying capacity | 250Vac/220Vdc, 5A |
Output type | Passive (NO/NC) |
Address | 1~99 |
Communication interface | |
Electrical characteristics | RS485 |
Transmission method | Asynchronous |
Communication protocol | Modbus RTU |
Communication medium | Shielded twisted pair |
Environment | |
Working temperature | -30 ~ 70°C |
Storage temperature | -40 ~ +85°C |
Humidity | 5~95%RH |
Electromagnetic compatibility | |
Electrostatic discharge test | IEC 60255-22-2:2008. level-4 |
Fast transient dry resistance test | IEC 60255-22-4:2008. level-A |
1mhz burst interference test | IEC 60255-22-1-2007. level-3 |
Electrical disturbance test | IEC 60255-22-2:2008.level-3 |
Surge immunity test | IEC 60255-22-5:2008 |