SEL Arc Flash Relay SEL-751

The SEL Arc Flash Relay SEL-751 is a versatile protection relay for industrial and utility feeders. It offers advanced features like arc-flash mitigation, fault location, and high-impedance fault detection. With flexible I/O options and support for various communication protocols, including IEC 61850 and Modbus, the SEL-751 can be easily integrated into modern power systems.

  • Feeder Protection
  • Arc-Flash Mitigation
  • High-Impedance Fault Detection
  • Automation and Control
  • LEA Sensor Inputs & Sensitive Neutral Input
  • Reliable Protection in Harsh Environments

 

Contact us
Category:

Features of SEL Arc Flash Relay

  • Rapid Detection and Response: Detects arc-flash hazards within 2 milliseconds and initiates a trip signal to the circuit breaker.
  • Minimized Equipment Damage: Reduces equipment damage during arc-flash events, improving system availability.
  • Coordinated Protection: Integrates with upstream protection systems using SEL Mirrored Bits or IEC 61850 GOOSE messaging to ensure coordinated fault clearing.
  • Versatile Installation: Suitable for both new and existing installations, including retrofitting SEL-751 relays.
  • Robust Communication: Supports multiple communication protocols, including Ethernet-based protocols like Modbus TCP, DNP3, and IEC 61850.
  • Reliable and Durable: Designed to operate in harsh environments with a wide temperature range and backed by a 10-year warranty.
  • Arc-Flash Mitigation: detect arc flash by the combined light and high-speed overcurrent detection

 

Specification of SEL Arc Flash Relay

Basic parameters
Rated working voltage DC24V
AC current 5A or 1A (specify when ordering)
Frequency 50HZ
Working power consumption Working normally, ≤ 3W

Protection operates, ≤ 6W

AC current loop consumption < 1VA/phase (IN =5A);

< 0.5VA/phase (IN =1A);

Current working range 0.08In~10In
Time working range 0~99s
Setting accuracy ≤±5%;
Time accuracy <±1%*setting time+20ms
The whole group action time Single criterion ≤ 7ms

Double criterion ≤ 20ms

Arc signal input
Input type Passive optical signal
Input quantity 3
Interface type: Optical fiber
Output contact capacity
A) Export relay: (3 routes)
Contact rated current carrying capacity 250Vac/220Vdc, 5A
Output type Passive (NO/NC)
B) Signal relay: (1 way)
Contact rated current carrying capacity 250Vac/220Vdc, 5A
Output type Passive (NO/NC)
Address 1~99
Communication interface
Electrical characteristics RS485
Transmission method Asynchronous
Communication protocol Modbus RTU
Communication medium Shielded twisted pair
Environment
Working temperature -30 ~ 70°C
Storage temperature -40 ~ +85°C
Humidity 5~95%RH
Electromagnetic compatibility
Electrostatic discharge test IEC 60255-22-2:2008. level-4
Fast transient dry resistance test IEC 60255-22-4:2008. level-A
1mhz burst interference test IEC 60255-22-1-2007. level-3
Electrical disturbance test IEC 60255-22-2:2008.level-3
Surge immunity test IEC 60255-22-5:2008