InsulGard Eaton Partial Discharge Monitoring

Contact us

Feature of Eaton Partial Discharge Monitoring

  • Ongoing internet surveillance.
  • Operates cable connections, bus ducts, switchgear, generators, motors, and dry-type transformers in unit substations.
  • More sophisticated filters improve precise tracking.
  • The online interface makes it simple to keep an eye on the state of the gadget.
  • Best-in-class sensing capability is provided by innovative sensor technology.
  • Service for remote monitoring offered by EESS group.
  • either retrofitted into already-existing equipment or factory-installed in new equipment.

 

Applications of Eaton Partial Discharge Monitoring

  • Generators
  • Motors
  • Switchgear
  • Unit substation dry-type transformers
  • Bus duct
  • Cable connections

 

Specification of Eaton Partial Discharge Monitoring

APPLICATIONS HV and MV equipment (motors, including VFD, switchgear, generators, bus ducts, cable terminations, transformers, etc.)
MOUNTING OPTIONS In NEMA 4X enclosure
Panel Mount
Door (flush) mount
INSTALLATION CATEGORY II
TEMPERATURE RANGE -40°C – +80°C (+70°C for enclosure mount)/UL certified for 00C – +700C ambient
RELATIVE HUMIDITY 0%RH – 90%RH
POLLUTION DEGREE 2
MAXIMUM ALTITUDE (M) 2000
POWER SOURCE 115V / 230V AC +/-10%
60 / 50 Hz
POWER CONSUMPTION OF DEVICE (VA MAX) 15VA
KEYPAD 4 arrows and 4 function keys
LEDS InsulGard Status: Normal
Warning (Alarm 1)
Alarm (Alarm 2)
Memory mode
Setting mode
NUMBER OF PD CHANNELS 15
PD CHANNEL MAGNITUDE DYNAMIC RANGE 68dB
FREQUENCY BANDWIDTH 1-20MHz
SYNCHRONIZATION TYPE Internal and external
INTEGRAL PD PARAMETERS Partial Discharge Intensity (PDI)
Maximum Pulse Magnitude (Qmax)
Pulse Repetition Rate, Trends of PDI and Qmax
Warning by PDI or Qmax
Alarm by PDI or Qmax and by Trends of PDI or Qmax
CONTINUOUS WATCH (HIGH PD ACTIVITY) FUNCTION Active between measurements
DATA RECORD TYPES Full/Brief (Test/Normal)
ADDITIONAL COMMUNICATION OPTIONS USB for communication with PC
Ethernet, webpage and FTP
REGULATORY AND STANDARDS COMPLIANCE UL 61010-1: Second Edition Standard for Electrical Equipment for Laboratory Use, with revisions dated 2008-10-28
FCC Part 15, Subpart B, Class A
CAN/CSA C22.2 No. 61010-1-04, Second Edition, with revisions through 2008-10-01
IEC61010-1:2001 and EN61010-1:2001
EN61326-1, EN61000-3-2, EN61000-3-3
IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11