ADL3000 Acrel Three Phase Multi Function Meter

ADL3000 Acrel Three Phase Multi Function Meter is a smart meter designed for power supply systems, industrial and mining enterprises, and utilities to calculate electricity consumption and manage electric demand. It features high precision, small size, and simple installation.  DTSD1352 can be used in all kinds of control systems, SCADA systems, and energy management systems. All meters meet the related technical requirements of electronic power meters in the IEC62053-21、IEC62053-22 standards.

Contact us

Features of Acrel Three Phase Multi Function Meter

  • IEC62053-21、IEC62053-22
  • Din rail mounted
  • kWh: Class 0.5S,kVarh:Class 2
  • AC 3×220/380V,3×380V,3×57.7/100V,3×100V
  • 3×1(6)A,3×10(80)A
  • U、I、P、Q、S、PF、kWh、kvarh
  • RS485(MODBUS-RTU)

Specifications of Acrel Three Phase Multi Function Meter

  • Communication: RS485(Modbus-RTU)
  • Rated U and I: AC 3×100V, 3×380V, 3×57.7/100V, 3×220/380V; 3×1(6) A, 3×10(80)A
  • Accuracy: kWh: Class 0.5S, kVarh: Class 2
  • Frequency: 50/60HZ(Optional), range: 45~65HZ
  • Display: 8 digits LCD display U, I, P, Q, PF, kWh and other energy consumption, Power measure (999999.99kWh)
  • Pulse output: Pulse output kWh/kvarh
  • Consumption: <10VA(Single phase)
  • Installation: DIN 35mm
  • Dimension(L*W*H): 126.5*88*69.5mm
  • Switch relay: Magnetic latching relay(ADL3000-E build-in)
  • Clock: ≤0.5s/d
  • Starting current: Direct connect: 0.004Ib, Connect via CT: 0.001ln
Voltage Reference voltage 3*57.7/100V,3*220/380V,3*100V,3*380V
Reference frequency 50Hz
Consumption <10VA(Single phase)
Current Maximum current 6A,80A
Starting current Direct connect:0.004lb

Connect via:0.001ln

Consumption <1VA(Single phase rated current)
Measurement performance Accuracy Class 0.5
Standards compliant IEC 62053-22:2003
Pulse Pulse width 80+20ms
Pulse constant 400imp/kWh

6400imp/kWh

Communication Interface RS485
Protocol Mod bus-RTU
Temperature range Work -25℃~55℃
Storage -40℃~70℃
Humidity ≤95%(No condensation)
Altitude <2000m