Masibus 9000U Series Loop Powered Isolator

Masibus 9000U+loop powered isolator is compact yet rugged 4 wire Isolator used for reliable Isolation and Attenuation of Industry Standard Field Signals. 9000U+ is available in Single or Dual output models. 9000U+ has higher noise rejection ratio that ensures accurate and noise free signal conditioning. It’s Slim DIN Rail mount design occupies less space and reduces cost of overall installation. With Dual output option this model also acts as Signal distributor. A typical application could be where the signal has to be distributed for indication on local panel, field control room, main control room or DCS system. The Isolator provides a good protection for sensitive system parts against voltage spikes etc.

Model 9000U+ has built-in transmitter power supply (TPS) to drive field transmitters delivering 4-20mA DC outputs signal. An exceptional feature of advanced extended universal power supply for the range of 20V to 265V DC or AC makes 9000U+ suitable for most of the power supply range available in field thus providing easy installation. Masibus’ 9000U+ Model offers an excellent accuracy and stability for reliable operation in hostile environments and full isolation safely separates input channel, each output channel and the power supply.

Contact us
Category:

Features

  • Available in Aux Powered (AP) and Loop Powered (LP) options
  • Extended Universal Power Supply Range: 20V to 265V DC or AC along with Safe and Sufficient Power For Field 2 Wire Transmitter (Aux Powered Model)
  • Switch Selectable Input/Output option (Aux Powered Model)
  • Rugged & accurate 4 wire and 2 wire isolator
  • Up to 2 outputs with Short Circuit Protection (Aux Powered Model)
  • Wide zero & span adjustment limits
  • 1.5KV AC Isolation between I/P, O/P and Supply
  • High CMRR and NMRR
  • High output Load Driving Capability
  • Lowest Long term Drift

 

Application

  • Field interface device
  • Transmitter Power Supply
  • Signal Repeater
  • Signal Converter
  • Factory automation
  • Impedance matching of transmitters and receiver instruments

Specifications

Input Type Voltage/Current
 

Input Range

‘L’ Version: 4-20mA

‘S’ Version: 4-20mA (Standard)

‘M’ Version: 0/4 to 20mA , 0/1 to 5V , 0 to 10V (DIP switch selection)

‘H’ Version: 4-20mA, HART Pass

 

Input Impedance

Current Input: ≤100 Ω (Loop Powered)

: ≤10 Ω (Aux Powered) Voltage Input: ≥1 MΩ

CMRR >100 dB
NMRR >70 dB
Temp-co ≤100ppm/°C
Output Type Voltage/Current
Loop Powered ‘L” Version: 4-20mA
 

Aux Powered

‘S’ Version: 4-20mA (Standard)

‘M’ Version: 0/4 to 20mA , 0/1 to 5V , 0 to 10V (DIP switch selection)

‘H’ Version: 4-20mA, HART Pass on o/p-1, 4-20mA, Standard on o/p-2

Response Time ≤50 ms
Accuracy ± 0.1% of FS
Output Load (Loop Powered) RLoad = [(Loop Supply Voltage – 10)/0.021]Ω
 

Output Load (Aux Powered)

mA: ≤750Ω@20mA (SOP),≤550Ω@20mA (DOP)

V: Load Current ≤ 5 mA

(e.g. for 0-5V: 5V/5mA ≥ 1 KΩ)

Output Loop status LED Green (Aux Powered, ‘S’ version only)
TPS Output (Aux Powered) ≈22VDC (±10%) @20mA
Supply (Loop Powered) 10 to 36VDC with reverse polarity protection
Supply (Aux Powered) 20-265V DC/AC (50-60Hz)
Power Consumption (Aux Powered) ≤3W
Power ON status LED Red (Aux Powered only)
Loop Power Model Input to Output: Galvanic Isolation of 1.5KVAC for 1 minute
 

 

 

 

 

 

 

Aux Powered Model

Power to Input and Output :

·    Reinforced insulation according to IEC/EN 61010-1, rated insulation voltage

3KVAC (For CE marked 9000C SOP ‘S’ and ‘M’ Model)

·    Galvanic Isolation of 3KVAC for 1 minute (For CE marked and Non-CE Model)

Input to Output :

·    Functional insulation according to IEC/EN 61010-1, rated insulation voltage

1.5KVAC (For CE marked 9000C SOP ‘S’ and ‘M’ Model)

·    Galvanic Isolation of 1.5KVAC for 1 minute (For CE marked and Non-CE Model)

Output to Output :

·    Galvanic Isolation of 1.5KVAC for 1 minute (For Non-CE Model)

Mounting 35 mm DIN Rail
 

Dimensions in mm

12.5(W)x100.2(H)x115.2(D) mm (For SOP Aux

and Loop Powered Model) 17.5(W)x100.2(H)x115.2(D) mm (For DOP and

HART Pass SOP/DOP)

Enclosure Material PA66
 

Weight

100 gms. Approx for SOP (Aux and Loop Powered)

130 gms. Approx for DOP

Operating temperature 0 to 55 °C
Storage temperature -20 to 85 °C
Humidity 30% to 95% RH(Non-condensing)