Features
- Easy to select, install and use
- All essential features built into the drive for minimized number of external components
- Many built-in control functions for simplified automation and process control
- Straightforward settings menu and assistants for fast commissioning
- Energy efficiency features for optimal energy use
- Connect to any automation system or use stand-alone
- Wide availability and support
- Designed for reliability and consistent high quality
Application
- Machine tools
- Textile machines
- Woodworking machines
- Packaging machines
- Electronics
- Fans
- Pumps
- Air compressors
Specification
Input ratings | Input voltage range | 208-240 V; 380-500 V; 525-600 V |
Input voltage tolerance | +10%/-15% | |
Phase | Three phase | |
Frequency | 47 to 63 Hz | |
Short circuit rating (UL 508c) | 100,000 rms symmetrical amperes up to 600 V when input cables protected by
class T or similar type fuses |
|
Output ratings | Horsepower | 0.75 – 100 HP @ 230 VAC
0.75 – 350 HP @ 480 VAC 1.5 – 300 HP @ 575/600 VAC |
Overload capacity | Heavy duty = 150% for 60 seconds every 5 minutes Light duty = 110% for 60 seconds every 5 minutes | |
Frequency | 0-500 Hz | |
Voltage | 0 to maximum input voltage (RMS) | |
Motor types | Asynchronous AC induction motors, permanent magnet synchronous motors and synchronous reluctance motors | |
Protective | Overcurrent | Excessive output current |
features | DC overvoltage | High DC bus |
Overtemp | Drive heatsink above operating temperature, max ambient temperature exceeded | |
Short circuit | Short on motor output terminals | |
Undervoltage | Low voltage on drive input | |
Loss of reference | Analog input programmed for 4-20 ma but signal less than 4 ma | |
Motor overtemp | Excessive estimated motor temperature | |
Loss of keypad | Drive will trip if under keypad control and keypad communication is lost | |
Motor stall | Motor cannot achieve commanded speed due to excessive load | |
Ground fault | Ground fault detected in motor or motor cabling | |
Motor phase fault | Loss at one of the motor phases | |
Environmental | Temperature | 0 to 40°C (32 to 104°F). 0 to 55°C (32 to 131°F) w/ derate. No frost allowed. |
Cooling | Forced air | |
Enclosure | UL type 1 (IP21), UL type 12 (IP55) | |
Altitude | Sea level to 3300 ft. (1000 m) Derate 1% per 330 ft. (100 m) up to 13,128 ft. (4000
m) |
|
Humidity | 0 to 95% RH non-condensing | |
Vibration | Max. 1 mm (0.04 in.) (5 to 13.2 Hz), max. 7 m/s2 (23 ft/s2) (13.2 to 100 Hz)
sinusoidal |
|
Keypad display | Display | LCD graphical |
Keys | 8 key keypad with tactile response | |
Functions | Output status monitoring, digital speed control, parameter setting and display, diagnostic and fault log display, motor run, local/remote toggle, graphical monitoring | |
Remote mount | Keypad may be mounted up to 9 ft. using appropriate cable (see Options for kit) | |
Trip | Last three faults stored in fault history | |
Control | Switching frequency | 1, 4, 8, 12kHz (up to 150hp): 1 or 4kHz (over 150hp) |
specifications | Accel/decel | 0-1800 seconds |
Speed control accuracy | 20% of motor slip | |
Skip frequencies | Three configurable bands 0-max speed | |
PC setup software | Drive composer, drive composer pro | |
Maximum output frequency | 500 Hz | |
Selectable operating modes | 2-Wire, 3-Wire, Motor Potentiometer, Hand/Auto, PID | |
Analog inputs | Two single ended | 0 (2) to 10 V, Rin > 312kÙ single-ended
0 (4) to 20mA, Rin = 100 Ù single-ended |
Resolution | ± 1% | |
Analog outputs | Two current outputs | 0 to 20 mA, load < 500 Ù |
Resolution | ± 3% | |
Digital inputs | Six digital inputs | 15 V…24 VDC with internal or external supply |
Input impedance | Pull-up or pull-down (PNP or NPN) (DI1 to DI5); NPN (DI6)
2.4 kÙ |
|
Digital outputs | Three relay outputs | Form C |
Maximum switching voltage | 250 VAC/30 VDC | |
Maximum continuous current | 2 A/30 VDC or 250 VAC | |
Safety | Safe torque off (STO) | STO standard input; 17…30 VDC, 55 mA |