AP910P – Arc Flash Protective Relay

The AP9010P arc flash protective relay is designed to quickly detect and clear arc flash incidents in low-voltage (LV) and medium-voltage (MV) electrical networks. AP9010P limits damages to equipment, improve safety, avoid and protect personnel injuries.

The AP910P arc flash protective relay can be used as a stand-alone arc protection relay or applied in more complex switchgear layouts.

The AP910P arc flash protective relay is designed for the protection of all types of Industrial, Railway, Generation and Distribution networks.

Contact us
Category:

Features of AP910P Arc Flash Protective Relay

  • Wide range power supply (18-72Vdc or 80-265Vac/dc)
  • 3 phases and residual current detection (1/5A)
  • Max 12 arc light point sensors
  • Max 1 fibre loop sensor (option)
  • 2 high Speed Outputs (<5ms trip time)
  • 4 trip relays (7ms trip time)
  • 1 system failure relay
  • 1 binary output (24Vdc)
  • 2 binary inputs (24/110/220Vdc)
  • 1 push button
  • Non-volatile memory
  • 20 indication LED

 

Specification of AP900 Arc Flash Protective Relay

Features AP901 AP901S AP902 AP910F AP910P
Wide range power supply (18-72 Vdc or 92-265 Vac/dc)
Mounting Panel/rack Panel/rack Panel/rack Panel/rack Panel/rack
3 phases and residual current detection (1/5A)
Max number of point sensors 12 12 12
Max number of fibre loop sensors 1 (option) 3 3 1 (option)
High Speed Outputs (<5mstrip time) 2 2
Number of trip relays (7ms trip time) 4* 3* 4* 4* 4*
System failure relay 1 1 1 1 1
Binary outputs (24 Vdc) 1 3 1 1 1
Binary inputs (24 Vdc) 2 6 2 2 2
Push button
Non-volatile memory
Indication LEDs 12 17 11 19 20
Applicable Sensors
AS01 light point sensor unit (8,000 lux)
AS02 light and pressure point sensor unit (8,000 lux – 0.2 bar above ambient pressure)
AS06 plastic fibre optic loop sensor ✓ (option) ✓ (option)
AS07 glass fibre optic loop sensor ✓ (option) ✓ (option)

Wiring of AP910P Arc Flash Protective Relay

typical wiring of AP910P arc flash relay