BWT48/220 Series Rack Mount Inverter 48V

Contact us
Category:

Features

  • Standard 19″ Rack mount 2 RU Chassia;
  • Ture sine wave output(T.H.D <3%)
  • Large 128*64 digital LCD display data infomation, 4 LED display working;
  • 5 Routes Dry contact for system ( DC input fault, AC input fault, overload information, by-pass information and output fault)
  • RS232 & RS485 &Optional SNMP communication port;
  • Power-on self-test, soft output start, start auto restart while AC or DC is recovering;
  • Auto switch function: DC to AC, AC by pass, less than 5ms;
  • Real-time monitoring of the system operating status, audible and visual alarm;
  • Record the historical alarm message and can be queried;
  • Build in voltage regulator stabilize AC voltage;
  • Maintenance bypass/DC available;
  • Protection: Short load protection, over load protection, battery over/under voltage protection, over current, over temperature

Specifications

MODEL BWT48/220 series
INPUT
AC Input Voltage 170-270A
Battery Input Voltage 48Vdc
Battery Voltage Range 45.5-57Vdc
Cooling Fan Cool (Temp.Control Speed According to the output capacity)
DC Input Current 208AMax
Output Frequency 50Hz/60Hz±1%
PF 0.8
OUTPUT
Output Capacity 1000VA/ 2000VA/ 3000VA/ 4000VA/ 5000VA/ 6000VA/
8000VA/ 10000VA
Rated Output Capacity 800W/ 1600W/ 2400W/ 3200W/ 4000W/ 4800W/6400W/
7000W
Rated output Voltage 220VAC (Inverter Mode )
Rated Output Current 3.6A/ 7.3A/ 11A/ 14.5A/ 18.2A/ 21.8A/ 29A/ 36.3A
Output Voltage Range 220Vac(Tolerance ±1.5% @Inverter Mode)
Output Efficiency ≥85% (Inverter Mode)
Output Frequency 50Hz/60Hz
Frequency Range 43~67Hz
Output Wave Pure sine wave
THD ≤3% (Line Load)
Switch Time (By pass to Inverter mode) ≤6ms (With Load)
PROTECTIVE FEATURE
AC Under Voltage  Switch Protection ≤176VAC (Backlash voltage≥5Vac)
AC over Voltage  Switch protection ≥264VAC
Over-Temperature Yes (Auto Switch)
Battery under voltage protection point ≤20VDC
Battery Low-voltage alarm 22VDC±0.5
Battery overvoltage protection point ≥58VDC
Battery overvoltage recovery point ≤45VDC
Output Over Current Protection
Over Load Capacity Continue working 60s   @100%<load<120%
Over Load Capacity Continue working 10s   @ 121%<Load<150%
Over Temp. Protection Yes
short circuit Protection Yes (Don’t test under AC Connect)
Reverse connection protection Yes
Output OVP ≥264VAC(Inverter Mode)
Output low voltage alarm ≤176VAC (Inveter Mode)
SAFETY AND EMC
Dielectric strength(AC-Chassis) 3500Vdc/10mA//1min .No flash over, no breakdown, no arc (Only AC Input priority)
Dielectric strength(DC-Chassis) 750Vdc/10mA/1min. No flash over, no breakdown
LVD EN 60950-1
EMC/EMI EN 61000-6-3; EN 61000-6-1 ;IEC 61000-6-2 and IEC 61000-6-4
ROHS

 

IEC62321-4, IEC 62321-5,IEC 62321-6,IEC 62321-7,IEC 62321-8
ENVIRONMENT TEST PERFORMANCE
Ambient Temp. -20~ +50℃
High temperature operation 50±2℃ (rated load 24H)
Low temperature operation -20±2℃ (rated load 24H)
High temperature storage 80±2 ℃,24H
Low temperature storage -40±2℃,24H
Humidity 0~90%,No moisture condensation
Operating  Altitude (m) Altitude Full power up to 2000m.derating -2% / 100m, max altitude 5000m
COMMUNICATION
Rs232 & Rs485 Yes
SNMP Optional
Dry Contact 5 group
LCD DISPLAY
LCD Status Input and output Voltage, Frequency ,Output Current,Temp., Load Rate,LOGO etc.
Inverter Status

 

Normal Mains, Normal Inverter, Battery Under-voltage and output overload etc.
MEASUREMENT
Size W*D*H(mm) 482mm*347mm*88mm (1-4KVA)
482mm*430mm*88mm (5-6KVA)
482mm*470mm*176mm (8-10KVA)
Weight 11KG-30KG