DATAKOM DKM-185 Voltage Detection System

The DATAKOM DKM-185 Voltage Detection System is a safety device designed to warn of the presence of dangerous high voltages in medium voltage (MV) electrical systems. It works by measuring the voltage on busbars using a capacitive divider bridge. To ensure maximum safety, the LCD displays are powered directly from the isolator current, allowing them to function even if the auxiliary DC power supply is unavailable. The DKM-185 comes in two versions: a basic model without relays and a version with a built-in relay output. The relay version features a DC-ON LED that indicates when the auxiliary DC supply is active.

Contact us

In accordance with the EN61243-5 standard, the DKM-185 operates as follows:

  • If the voltage in any phase exceeds 45% of the nominal voltage (0.45Un), the corresponding display will light up and the relay (relay version only) will activate.
  • If a phase voltage falls below 10% of the nominal voltage (0.1Un), the corresponding display will turn off. When all phase voltages drop below 0.1Un, the relay (relay version only) will deactivate.

For safety, the unit is grounded and does not carry hazardous voltages itself. To verify operation, divided voltage readings are accessible on the front panel test terminals, which come with a watertight gasket for both testing and panel mounting.

Important Note: The DKM-185 is built to order based on specific application requirements. When placing an order, please provide the capacitive isolator value (in picofarads) and the busbar voltage for proper configuration.

Additional Information (Relay Version Only):

  • The relay version utilizes an isolated switch-mode power supply that does not affect the DC busbar polarity.

 

Features of Voltage Detection System

  • Wide operating voltage range (1kV-52kV)
  • EN61243-5 LRM conformal detection
  • Independent indicators for each phase
  • Test terminals (3 phase + ground)
  • 1 relay output (5Amp) (5Amp)
  • DC-ON led indicator
  • Wide DC supply range (19-150VDC)
  • Isolated power supply
  • Wide operating temperature range (-20…+70°C)

 

Specification of Voltage Detection System

Operating voltage range 1kV-52kV
Auxiliary supply 19-150V-DC
Power consumption maks. 1W
Relay output current 5 amps max
Relative humidity max. %95 (non-condensing)
Dimension 100x53x52.5mm
Panel cutout 92x45mm minimum. (DIN 1/8)
Weight 150g
IP Protection IP20
Enclosure High temperature, flame retardant ABS/PC
Mounting Flush mounted with rear retaining brackets