Feature of CSMPM Digital Motor Protection Relay
- Digital Relay with built-in MCU (Micro Processor Control Unit).
- Multiple protection: Overload / Phase failure / Stall /Asymmetry / Phase reverse/ Earth Fault.
- Current setting 0.5-6A & 5-60A.
- Current setting 0.5-6A can be used up to 600A with external Ct’s
- Fault diagnostic seven-segment display of fault & values.
- Digital Ammeter function.
- Time setting: Inverse time (0-60 sec), Definite time (0-60 sec) starting & Delay time (0-30
sec) operating time. - Accuracy: Current / Time + 5% of setting.
- Fail-safe operation
- Alert function (60-110% of set current).
- Inverse / Definite time characteristics, site selectable.
- C.T. ratio setting in CSMPM-06 frame only.
Specification of CSMPM Digital Motor Protection Relay
Wiring | Screw type (S)/Tunnel (T) |
Panel mount | Unit or Extension |
Operation time | Select either reverse time characteristics or definite time |
Over current protection | According to the setting time |
Phase failure protection | 3 sec. |
Reverse phase protection | Within 0.1 sec. |
Asymmetry | 5 sec. |
Stall | 5 sec |
Lock | Within 0.5 sec |
Under current | 3 sec |
Ground fault | Within 0.05~1 sec. Selectable (0.05~1.0sec) |
Short circuit | Within 50ms |
Alarm | Variable (60~110% of the setting current) |
Insulation resistance | Over DC500V 100MW |
Surge impulse voltage(IEC1000-4-5) | 1.2x50ms 6kV (Apply standard wave form) |