Features of DPA AC Power Transducer
- Measurement accuracy of 2/0.5
- Customizable parameter support
- RMS measurement and output
- Swift 500ms response time
- Easy installation on a 35mm Din rail
- Reliable high load capacity
- Minimal output ripple
- Wide selection of D.C. current and voltage inputs available
Application of DPA AC Power Transducer
- Suitable for medium and low voltage systems.
- Used for metering distribution feeders, transformers, generators, capacitor banks, and motors.
- Offers a measuring converter with the optional ability to associate an instantaneous parameter with one of the available analog outputs (0-20 mA / 4-20 mA).
- Typically employed to prevent earth loops, which occur when a grounded measuring source is connected to a computer or data logger that is also grounded.
- Applications include motor control, panel power monitoring, power consumption monitoring and control, power distribution systems, intelligent building and automation power management systems, and power testing equipment.
Specification of DPA AC Power Transducer
Signal Inputs | |
Input rating | DPA 4-20mA, 0-20mA |
Overload | 1.2 times rated continuous; 5sec @ 10 times of rated current 1sec @ 2 times of rated voltage |
Burden | 0.5VA |
Measurement Output | |
Standard outputs | 4~20mA or 0~5V |
(others on request) | 0~20mA; |
5~10V; | |
0~10V; | |
Ripple | <0.5% peak to peak |
Load Resistance | Current output: 0<Lr<510Ω; |
Voltage output: Lr>10KΩ | |
Measurement Accuracy | |
Reference IEC 60688 | 0.5% or 0.2% @ F.S. |
Adjustment | Potentiometer “ZERO” and “SPAN” |
Frequency influence | <0.02% per Hz |
Load influence | <0.25% of F.S. for specific load range |
Auxiliary Supply | |
Rating | 85-265Vac/dc, Optional 12V, 24V, 48VDC |
Consumption | <3VA |
Galvanic isolation between I/O and AUX | |
Test voltage | 2KV RMS 50Hz for 1 minute |
impulse | 4KV 1.2/50µsec waveform |
Temperature requirements | |
Operating | -10~55℃ |
Storage | -40~70℃, 20 ~ 93%RH;Noncondensing |