Feature
- Short circuit Fault:Red mechanical flag and three red ultra-bright blinking LEDs.
- Earth-fault:Red mechanical flag and three red ultra-bright blinking LEDs
- Low Battery Warning: Red mechanical flag.
- Parameter Adjust:The parameters can be adjusted by dial switches during production.
- Power Supply:Lithium battery, type AA 2.7Ah/3.6V.
Specification
DYX-FF Remote Cable Line Fault Indicator
General | |
Applicable voltage range |
6~35KV (should confirm before production)
|
Applicable current range | 0~630A (should confirm before production) |
Applicable power frequency range | 45~60Hz (should confirm before production) |
MTBF | more than 70000H |
Impulse current withstand | 31.5kA for 2s |
Degree of protection | IP67 |
Weight | less than 540g |
Outline dimension | Ф75mm * 115mm |
EMC | |
Electrostatic discharge |
Can withstand the GB/T 17626.2 of the IV level of electrostatic discharge interference test
Communication discharge: + 8KV
Air discharge: + 15KV
|
EFT/B immunity test |
Can withstand the GB/T 17626.12 of the IV class fast pulse group interference test
Voltage peak value: 2KV
Frequency: 5KHz & 100KHz
|
Radiated susceptibility | Can withstand the GB/T 17626.3 of the IV level RF electromagnetic field immunity Field strength: 30V/m |
Surge immunity |
Can withstand the GB/T 17626.5 of the IV level surge (impact) interference test
Common mode voltage: 4KV ± 10%
Differential mode voltage: 2KV ± 10%
|
Power frequency magnetic field immunity | Can withstand the GB/T 17626.8 of the V level power frequency magnetic field immunity interference test Magnetic field intensity: 100A/m |
Damped oscillatory magnetic field immunity | Can withstand the GB/T 17626.10 of the V level damping oscillation magnetic field immunity test Damped oscillatory magnetic field intensity peak value: 100A/m |
Environmental | |
Environment temperature | Operation temperature: -35℃~80℃(-31~+176℉) Storage temperature: -40℃~85℃(-40~+185℉) |
Relative humidity | 5~95%( No condensing) |
Altitude | ≤4000m |