Feature
- Universal 180-550VAC or 254-780VDC input voltage
- Single/Two phase both available
- Operating ambient temperature range: -40℃ to +70℃
- Low ripple & noise, high efficiency
- DC OK function
- Built-in active PFC function
- 150% peak load for 5 seconds
- Output short circuit, over-current, over-voltage, over-temperature, constant current limit protection
- OVC III, 2000m altitude (UL62477 standards)
- Safety according to UL/EN/BS EN62368, UL61010, UL62477
Specification
Input Specifications | ||||||
Item | Operating Conditions | Min. | Typ. | Max. | Unit | |
Input Voltage Range | AC input | 180 | — | 550 | VAC | |
DC input | 254 | — | 780 | VDC | ||
Input Frequency | 47 | — | 63 | Hz | ||
Input Current | 230VAC | — | — | 2.0 | A | |
400VAC | — | — | 1.0 | |||
Inrush Current | 400VAC | Cold start | — | — | 110 | |
Power Factor | 230VAC | — | 0.93 | — | — | |
400VAC | — | 0.90 | — | |||
Leakage Current | 480VAC | 1mA RMS Max. | ||||
Input Temporary Over-voltage | Rated load output, 600VAC input | 5s/time, interval 10s, product without damaging | ||||
Hot Plug | Unavailable |
Output Specifications | |||||
Item | Operating Conditions | Min. | Typ. | Max. | Unit |
Output Voltage Accuracy | Full load range | — | ±1.0 | — | % |
Line Regulation | Rated load | — | ±0.5 | — | |
Load Regulation | 400VAC | — | ±1.0 | — | |
Ripple & Noise* | 20MHz bandwidth (peak-to-peak value) | — | — | 150 | mV |
Temperature Coefficient | — | ±0.03 | — | %/°C | |
Short Circuit Protection | Hiccup, continuous, self-recovery | ||||
Over-current Protection | ≥150% Io, hiccup, self-recovery | ||||
Over-voltage Protection | 24V output | ≤33V | Output voltage clamp or hiccup | ||
48V output | ≤65V | ||||
Over-temperature Protection | 400VAC, rated load | Output voltage turn off, self-recovery |
Minimum Load | 0 | — | — | % | ||
Start-up Time | 230VAC | — | 1.5 | 3.0 | s | |
400VAC | — | 0.8 | 1.5 | |||
DC OK Signal** | Resistive load | 30VDC/1A Max. | ||||
Hold-up Time | Room temperature, full load | 230VAC | — | 18 | — | ms |
400VAC | — | 18 | — | |||
Note: *The “Tip and barrel method” is used for ripple and noise test, output parallel 47uF electrolytic capacitor and 0.1uF ceramic capacitor, please refer to Enclosed Switching Power Supply Application Notes for specific information.
**DC OK Signal: When the output voltage is normal, the relay is connected. When the output voltage is abnormal (<90%Vo), the relay is disconnected. |
General Specifications | ||||||
Item | Operating Conditions | Min. | Typ. | Max. | Unit | |
Isolation |
Input – output |
Electric Strength Test for 1min., leakage current<5mA |
4000 | — | — |
VAC |
Input – PE | 2000 | — | — | |||
Output – PE | 500 | — | — | |||
Output – DC OK | 500 | — | — | |||
Insulation Resistance |
Input – output |
500VDC |
100 |
— |
— |
MΩ |
Input – PE | ||||||
Output – PE | ||||||
Operating Temperature | -40 | — | +70 |
℃ |
||
Storage Temperature | -40 | — | +85 | |||
Operating Humidity | Non-condensing | — | — | 95 | %RH | |
Storage Humidity | — | — | 95 | |||
Power Derating |
-40℃ to -30℃ | 3.0 | — | — | %/℃ | |
+50℃ to +70℃ | 2.0 | — | — | |||
180VAC – 200VAC | 0.5 | — | — | %/VAC | ||
2000-5000m | 3.5 | — | — | %/Km | ||
Safety Standard | Design refer to UL508, UL61010-1, UL62477-1, UL60664, UL/EN/BS EN62368-1, GB4943.1 & EN61558-1 | |||||
Safety Class | CLASS I | |||||
MTBF | MIL-HDBK-217F@25℃>300,000 h |