OHR-215 Isolated HART Temperature Transmitter

OHR-215 Isolated HART Temperature Transmitter (round card) is used for the signal input of resistance temperature detector (RTD) and thermocouple (TC) and 4 – 20mA analog output of the two-wire system and can be installed in the sensor(Form B) through the HART protocol configuration.

Contact us

Features

  • Full switching of temperature signal
  • Using photoelectric isolation technology
  • RS485 communication interface
  • Relay alarm output
  • Low power consumption and low heat generation
  • Support transmission output
  • Smart appearance and high cost performance
  • Transmission accuracy: 0.2%FS (20°C)
  • I/O/power isolated from each other

 

Applications

  • Detection, conversion and transmission of temperature in industrial automation control
  • In the field of environmental monitoring, the measurement and transmission of atmospheric temperature, water temperature, ground temperature and other parameters are realized
  • Used in weather stations, hydrological stations, geological exploration and other fields
  • In the field of medical equipment, it realizes the monitoring and transmission of patient body temperature.
  • Applied to the cold chain logistics industry to monitor and record the ambient temperature of logistics vehicles and cold storage

 

Specification

Input
Input signal Resistance temperature detector (RTD), thermocouple (TC)
Cold-junction compensation -20 -60℃
temperature scope
Compensation precision ±1 ℃
Output
Output signal 4-20mA, overlaid HART protocol
Load resistance RL≤(Ue-12)/0.021
Output current of upper and lower

 

limit overflow alarm

IH=21mA, IL=3.8mA
Power supply
Supply voltage DC12-40V
Other parameters
Temperature drift 0.0075%FS/℃
Response time Reach to 90% of the final value for700ms
Used environmental temperature -40 – 80℃
Storage temperature -40 – 100℃
Insulation strength (between input

 

and output)

1500Vrms (1 min, without spark)
Insulation resistance (between

 

input and output)

≥100MΩ(under the 500 VDC)
Aseismicity 4g/2 – 150Hz
Installation angle Unlimited
Installation area B-type top cassette installation
Electromagnetic compatibility Conform to GB/T18268 industrial equipment application

 

requirements (IEC 61326-1)