RM22-UA under over voltage protection relay schneider

This Harmony RM22-UA under over voltage protection relay schneider allows monitoring of voltage control in single phase networks. This modular multi function single phase voltage control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slim form-factors with 22.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a diagnostic button, sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC.

Contact us
Category:

Specifications of RM22-UA Overvoltage and Undervoltage Control Relay

Main
Range of product Harmony Control Relays
Relay type Voltage control relay
Product or component type Voltage control relay
Network number of phases 1 phase
Supply circuit type DC
Relay name RM22UA
Relay monitored parameters Undervoltage and overvoltage in window mode
Overvoltage or undervoltage detection
time delay Adjustable 0.1…30 s, +/- 10 % of the full scale value on crossing the threshold Tt
Switching capacity in VA 2000 VA
Minimum switching current 10 mA at 5 V DC
Maximum switching current 8 A AC
Power consumption in VA 3.5 VA AC
Measurement range 15…500 V voltage AC/DC 50/60 Hz
Utilisation category AC-15 conforming to IEC 60947-5-1
DC-13 conforming to IEC 60947-5-1
AC-1 conforming to IEC 60947-4-1
DC-1 conforming to IEC 60947-4-1
Contacts type and composition 2 C/O
Complementary
Reset time 1500 ms at maximum voltage
Maximum switching voltage 250 V AC
Supply voltage limits 20.4…264 V AC/DC
Maximum power consumption in W 1.5 W DC
Immunity to microbreaks 10 ms
Resistance across terminals 150 kOhm at E2-M terminals
300 kOhm at E1-M terminals
500 kOhm at E3-M terminals
Output contacts 2 C/O
Nominal output current 8 A
Maximum measuring cycle 100 ms measurement cycle as true rms value
Hysteresis 3 % fixed of full scale for window mode
5…50 % adjustable of threshold setting
delay at power up 600 ms
Repeat accuracy +/- 0.5 % for input and measurement circuit
+/- 2 % for time delay
Measurement error < 1 % over the whole range with voltage variation
0.05 %/°C with temperature variation
Response time <= 500 ms
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 100 MOhm at 500 V DC
insulation Between supply and measurement
Connections – terminals Screw terminals, 2 x 0.5…2 x 2.5 mm² (AWG 20…AWG 14) solid without cable end
Screw terminals, 2 x 0.2…2 x 1.5 mm² (AWG 24…AWG 16) flexible with cable end
Screw terminals, 1 x 0.5…1 x 3.3 mm² (AWG 20…AWG 12) solid without cable end
Screw terminals, 1 x 0.2…1 x 2.5 mm² (AWG 24…AWG 14) flexible with cable end
Tightening torque 0.6…1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Mounting support 35 mm DIN rail conforming to IEC 60715
Electrical durability 100000 cycles
Mechanical durability 10000000 cycles
Contacts material Cadmium free
Safety reliability data MTTFd = 308.2 years
B10d = 290000
Width 22.5 mm
Net weight 0.11 kg
Functionality Undervoltage and overvoltage in window mode
Compatibility code RM22
Environment
Electromagnetic compatibility Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1
Immunity for industrial environments conforming to IEC 61000-6-2
Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
Emission standard for industrial environments conforming to IEC 61000-6-4
Electrostatic discharge – test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge – test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test – test level: 10 V/m level 3 conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test – test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4
Electrical fast transient/burst immunity test – test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4
Surge immunity test – test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5
Surge immunity test – test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5
Conducted and radiated emissions class B group 1 conforming to CISPR 11
Conducted and radiated emissions class B conforming to CISPR 22
Standards IEC 60255-1
product certifications RCM
UL
EAC
CSA
CE
GL
CCC
Ambient air temperature for storage -40…70 °C
Ambient air temperature for operation -20…50 °C at 60 Hz
-20…60 °C at 50 Hz
Relative humidity 93…97 % at 25…55 °C conforming to IEC 60068-2-30
Vibration resistance 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
1 gn (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6
0.035 mm (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
Shock resistance 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27
5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
IP degree of protection IP20 (terminals) conforming to IEC 60529
IP40 (housing) conforming to IEC 60529
IP50 (front panel) conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Dielectric test voltage 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27