Specification
Range of Product | Zelio Time |
---|---|
Product or Component Type | Industrial timing relay |
Component name | RE7 |
Time delay type | A |
Time delay range | 0.05 s…300 h |
discrete output type | Relay |
---|---|
Contacts material | 90/10 silver nickel contacts |
Width pitch dimension | 0.89 in (22.5 mm) |
[Us] rated supply voltage | 110…240 V AC 50/60 Hz 24 V AC/DC 50/60 Hz |
Voltage range | 0.85…1.1 Us |
Connections – terminals | Screw terminals, 2 x 1.5 mm² flexible with cable end Screw terminals, 2 x 2.5 mm² flexible without cable end |
Tightening torque | 5.31…9.74 lbf.in (0.6…1.1 N.m) |
Setting accuracy of time delay | +/- 10 % of full scale |
Repeat accuracy | +/- 0.2 % |
Temperature Drift | < 0.07 %/°C |
Voltage drift | < 0.2 %/V |
Minimum pulse duration | 20 ms |
Reset time | 50 ms |
Maximum switching voltage | 250 V AC/DC |
Mechanical durability | 20000000 cycles |
[Ith] conventional free air thermal current | 8 A |
Maximum [Ie] rated operational current | 2 A DC-13 24 V 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 0.1 A DC-13 250 V 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 0.2 A DC-13 115 V 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 3 A AC-15 158 °F (70 °C) IEC 60947-5-1/1991/VDE 0660 |
Minimum switching capacity | 10 mA 12 V |
Marking | CE |
Overvoltage category | III IEC 60664-1 |
[Ui] rated insulation voltage | 250 V between contact circuit and control inputs IEC 250 V between contact circuit and power supply IEC 300 V between contact circuit and control inputs CSA 300 V between contact circuit and power supply CSA |
Supply disconnection value | > 0.1 Uc |
Operating position | Any position without derating |
Surge withstand | 2 kV IEC 61000-4-5 level 3 |
Power consumption in VA | 0.7 VA 24 V 1.8 VA 110 V 8.5 VA 240 V |
Maximum power consumption in W | 0.5 W 24 V |
Terminal description | (15-16-18)OC_OFF (B1-A2)CO ALT |
Height | 3.07 in (78 mm) |
Width | 0.89 in (22.5 mm) |
Depth | 3.15 in (80 mm) |
Net Weight | 0.33 lb(US) (0.15 kg) |
Immunity to microbreaks | 3 ms |
---|---|
Standards | EN/IEC 61812-1 |
Product Certifications | CSA GL UL |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Ambient Air Temperature for Operation | -4…140 °F (-20…60 °C) |
Relative humidity | 15…85 % 3K3 IEC 60721-3-3 |
Vibration resistance | 0.35 mm 10…55 Hz)IEC 60068-2-6 |
Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
IP degree of protection | IP20 terminals) IP50 housing) |
Pollution degree | 3 IEC 60664-1 |
Dielectric strength | 2.5 kV |
Non-dissipating shock wave | 4.8 kV |
Resistance to electrostatic discharge | 6 kV in contact IEC 61000-4-2 level 3 8 kV in air IEC 61000-4-2 level 3 |
Resistance to electromagnetic fields | 9.14 V/m (10 V/m) IEC 61000-4-3 level 3 |
Resistance to fast transients | 2 kV IEC 61000-4-4 level 3 |
Disturbance radiated/conducted | CISPR 11 group 1 – class A CISPR 22 – class A |