The Schneider VigiPacT RH197P is an ideal solution for ensuring safety and reliability in your electrical system.
How does the Schneider Residual Current Monitoring System work?
- Mounted on a front panel for easy access.
- Measures leakage current through a separate toroid sensor (not included).
- Trips the connected circuit breaker if the leakage current exceeds a user-defined threshold
Features of Schneider Residual Current Monitoring System
- Wide range of sensitivity: Adjustable from 30 mA to 30 A for tailored protection.
- Customizable time delay: Selectable between instant and 4.5 seconds to suit specific applications.
- Type A earth leakage protection: Covers AC, pulsating DC, and mixed AC/DC residual currents.
- Flexible reset options: Choose between manual or automatic reset after a fault.
- High voltage monitoring: Up to 1000 VAC for a wider range of applications.
- Durable construction: IP40 enclosure protects against dust and limited water ingress.
- Schneider Electric compatibility: Requires a compatible Schneider Electric type A toroid or rectangular sensor (sold separately).
Specification of Schneider Residual Current Monitoring System
| Range | VigiPacT |
|---|---|
| Device short name | RH197P |
| product or component type | Residual current protection relay |
| relay application | Protection relay |
| mounting support | Front panel |
| Earth-leakage protection class | Type A |
| Type of setting | Selector |
| Residual earth-leakage sensitity adjustment type | Adjustable 19 settings |
| Earth-leakage sensitivity | 0.03…30 A |
| Earth-leakage time delay | Instantaneous for 0.03 A Adjustable 7 settings 0…4.5 s for 0.03…30 A |
| Alarm threshold | 100 % |
| Current sensors compatibility | VigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor |
| [Ithe] conventional enclosed thermal current | 8 A |
| Minimum load | 10 mA at 12 V |
| [Us] rated supply voltage | 220…240 V AC 50/60 Hz 70…110 % |
| Power consumption in VA | 4 VA |
| Monitored distribution system | 1000 V – AC at 50/60 Hz (maximum) 1000 V – AC at 400 Hz (maximum) |
| Earthing system | TT IT TN-S |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Reset | Manual reset Automatic reset |