The Schneider VigiPacT RH197P is an ideal solution for ensuring safety and reliability in your electrical system.
How does the Schneider Residual Current Monitoring System work?
- Mounted on a front panel for easy access.
 - Measures leakage current through a separate toroid sensor (not included).
 - Trips the connected circuit breaker if the leakage current exceeds a user-defined threshold
 
Features of Schneider Residual Current Monitoring System
- Wide range of sensitivity: Adjustable from 30 mA to 30 A for tailored protection.
 - Customizable time delay: Selectable between instant and 4.5 seconds to suit specific applications.
 - Type A earth leakage protection: Covers AC, pulsating DC, and mixed AC/DC residual currents.
 - Flexible reset options: Choose between manual or automatic reset after a fault.
 - High voltage monitoring: Up to 1000 VAC for a wider range of applications.
 - Durable construction: IP40 enclosure protects against dust and limited water ingress.
 - Schneider Electric compatibility: Requires a compatible Schneider Electric type A toroid or rectangular sensor (sold separately).
 
Specification of Schneider Residual Current Monitoring System
| Range | VigiPacT | 
|---|---|
| Device short name | RH197P | 
| product or component type | Residual current protection relay | 
| relay application | Protection relay | 
| mounting support | Front panel | 
| Earth-leakage protection class | Type A | 
| Type of setting | Selector | 
| Residual earth-leakage sensitity adjustment type | Adjustable 19 settings | 
| Earth-leakage sensitivity | 0.03…30 A | 
| Earth-leakage time delay | Instantaneous for 0.03 A Adjustable 7 settings 0…4.5 s for 0.03…30 A  | 
| Alarm threshold | 100 % | 
| Current sensors compatibility | VigiPacT TOA earth leakage current sensor VigiPacT A earth leakage current sensor VigiPacT L earth leakage current sensor  | 
| [Ithe] conventional enclosed thermal current | 8 A | 
| Minimum load | 10 mA at 12 V | 
| [Us] rated supply voltage | 220…240 V AC 50/60 Hz 70…110 % | 
| Power consumption in VA | 4 VA | 
| Monitored distribution system | 1000 V – AC at 50/60 Hz (maximum) 1000 V – AC at 400 Hz (maximum)  | 
| Earthing system | TT IT TN-S  | 
| [Uimp] rated impulse withstand voltage | 8 kV | 
| Reset | Manual reset Automatic reset  | 
								



