Advantages of Siemens 760 P/E Positioner
- Universal design and choice of interchangeable NAMUR IEC 534-6 rectilinear VDI/VDE 3845 rotary mountings provide wide application flexibility
- Double-acting or single-acting service and split ranging afford application versatility in a single unit
- Non-interaction of the zero and span adjustments and CAMLOC™ cam locking mechanism significantly reduce the calibration and setup time
- Modular design reduces inventory because it allows interchangeable spare parts
- Comes standard with 3 cams-linear, quick opening, and equal % for application versatility
Specifications of Siemens 760 P/EPositioner
Specifications | |
Actuator Type | Double-Acting Single Action |
Temperature Range | 760P: -40°F to +185°F (-40°C to 85°C)/Optional: -20°F to +300°F (-29°C to +148°C)
760E: -40°F to +167°F (-40°C to +75°C) |
Ingress | NEMA 4X IP 65 Connections Pneumatic – 1/4″ NPT Gauge – 1/8″ NPT Electrical – 3/4″ NPT, 25 mm Exhaust – 1/4″ NPT |
Finish | Epoxy/Polyester Powder Coat Output Configuration Single or Double Acting |
Action | Direct or Reverse Supply Pressure 150 psig |
Air Consumption | Standard Spool = 0.5 scfm Low Gain Spool = 0.5 scfm High Flow Capacity Spool = 1.0 scfm (typical) Flow Capacity (at 60 psi with 25% drop) 0 scfm (Cv = 0.3) Standard 0 scfm (Cv = 0.6) Optional Input Signal 760P: 3-15 psig, 3-27 psig, 50% split range 760E: 4-20 mA @ 40 VDC max. (resistance 260 ohms, reactance 260 ohms), 50% split range |
Mechanical Feedback | 90°, rotary standard Characterization Equal Percentage, Quick Opening, Linear |
Pressure Gain | 160:1 @ 60 psig standard |
Span | Adjustable -60% to +25% of normal span Zero Adjustable -10% to +60% of normal span |
Performance Specifications | |
Linearity (Independent) | 760P: 0.5% of normal span (typical) 760E: 0.75% of normal span (typical) Hysteresis 760P: 0.75% of normal span (typical) 760E: 1.0% of normal span (typical) Deadband Less than or equal to 0.25% of span |
Repeatability | Within 0.5% of span Supply Pressure Effect Less than 2% of span for a 5 psi change in |
Intrinsically Safe | Class I, Division 1, Groups A, B, C, D Class II, Division 1, Groups E, F, G Class III, Division 1 |
Non-incendive | Class I, Division 2, Groups A, B, C, D Suitable for: Class II, Division 2, Groups F, G Class III, Division 2 |
Enclosure | Type 4X per NEMA standard 250 Type IP65 per IEC standard 529 |