Feature:
√ • Full digital control, strong anti-jamming capability, and high computerization speed;
√ • The transfer time is ≤5ms; high reliability; manual and automatic switches are both available;
√ • Strong overload capacity; can be started under the full load
√ • Having input and output over-voltage and under-voltage, over-temperature and overload protection functions, etc.;
√ • The front panel is equipped with a control panel (NA for the one less than 10K), so the information about the condition is obvious.
TECHNICAL SHEET
| Product Size | Rated Capacity | 6KVA | 10KVA | 15KVA | 20KVA | 30KVA |
| Size (W×H×D)(mm) | 19″1U | 19″3U | ||||
| 490*44*343 | 490*132*404 | |||||
| Switch Time | ≤4mS | |||||
| AC Input | Rated Voltage | 220VAC | ||||
| Rated Voltage Range | 190~250VAC | |||||
| Rated frequency | 50HZ | |||||
| Valid working Voltage | 220Vac±12.5%,backlash±5V | |||||
| frequency | 50Hz±10%,backlash±0.2Hz | |||||
| Power off Voltage | ≤120Vac Or ≥260Vac,backlash±5V | |||||
| Power off frequency | ≤42.5Hz or ≥57.5Hz,Power off Voltage=±0.2Hz | |||||
| Overload capacity | Load current <105%, continue running
Load current: >105%, 60mS power off |
|||||
| Communication Interface | RS485 | |||||
| Environment | Insulation strength | 2KVac,1min | ||||
| Noise (1m) | <45dB | <50dB | ||||
| Working environment temperature | -10~50℃ | |||||
| Transportation and storage temperature | -40~70℃ | |||||
| Humidity | 0~90%, non condensing | |||||
| altitude(M) | ≤3000m,1500~3000m, Rise every 100m, 1% derated. | |||||