Specifications
General technical data | ||
size of contactor can be combined company-specific | S00, S0, S2, S3 | |
product component semi-conductor output | No | |
product extension required remote control | No | |
product extension optional remote control | No | |
insulation voltage for overvoltage category III according to IEC 60664 with degree of pollution 3 rated value | 300 V | |
test voltage for isolation test | 1.5 kV | |
degree of pollution | 3 | |
surge voltage resistance rated value | 4 kV | |
test voltage for surge voltage test | 4 800 V | |
consumed current | ||
● at 24 V | 24 mA | |
● at 240 V | 7 mA | |
protection class IP of the terminal | IP20 | |
shock resistance according to IEC 60068-2-27 | 15g / 11 ms | |
vibration resistance according to IEC 60068-2-6 | 10 … 59 Hz: 0.35 mm, 60 … 150 Hz: 2g | |
mechanical service life (operating cycles) typical | 10 000 000 | |
mechanical service life (operating cycles) | ||
● with contactor 3R.2 of frame size S00 | 10 000 000 | |
● with contactor 3R.2 of frame size S0 | 10 000 000 | |
● with contactor 3R.2 of frame size S2 | 10 000 000 | |
● with contactor 3R.2 of frame size S3 | 10 000 000 | |
electrical endurance (operating cycles) at AC-15 at 230 V typical | 100 000 | |
electrical endurance (operating cycles) | ||
● with contactor 3R.2 of frame size S00 | 100 000 | |
● with contactor 3R.2 of frame size S0 | 100 000 | |
● with contactor 3R.2 of frame size S2 | 100 000 | |
● with contactor 3R.2 of frame size S3 | 100 000 | |
adjustable time | 0.05 … 100 s | |
relative setting accuracy relating to full-scale value | 15 % | |
minimum ON period | 35 ms | |
recovery time | 150 ms | |
reference code according to IEC 81346-2 | K | |
relative repeat accuracy | 1 % | |
influence of the surrounding temperature | ±1 % | |
power supply influence | ±1 % | |
Substance Prohibitance (Date) | 10/01/2009 | |
SVHC substance name |
Blei – 7439-92-1
Bleimonoxid (Bleioxid) – 1317-36-8
|