MMP Smart Electronic Motor Protection Relay

The MMP Smart Electronic Motor Protection Relay, also known as motor overcurrent relay, is manufactured by LS ELECTRIC Co., Ltd. This electronic motor protection relay is used to replace the motor thermal overload relays.

  • Current, voltage, and power measurement, power factor protection
  • Harmonic measurement (up to the 16th harmonic)
  • Modbus communication, and 4-20mA analog output

 

Contact us
Category:

Features of MMP Smart Electronic Motor Protection Relay

  • Versatile Design: Available in both one-body and separate-body configurations to suit various installation needs.
  • Advanced Communication: Equipped with RS485 Modbus and 4-20mA analog output for remote monitoring and control.
  • Customizable Protection: Offers a wide range of protection settings, including adjustable ground fault current sensitivity (30mA to 25A), and thermal heat build-up inverse time, inverse time, and definite time characteristics.
  • Simplified Installation: Can operate without external current transformers (CTs) up to 100A, reducing installation costs and complexity.
  • Precise Measurement: Provides accurate measurement of current, voltage, and energy with 1% accuracy.
  • Enhanced Functionality: Performs complex relay functions related to current, voltage, energy, and power factor.
  • Self-Diagnostic Capabilities: Continuously monitors its own health and system parameters for reliable operation.
  • Robust Protection: Offers dual protection capabilities and supports various motor starting modes.
  • User-Friendly Interface: Provides clear date information display, password protection, and total operating time monitoring.
  • Fault Recording and Analysis: Stores detailed information about fault occurrences for analysis and troubleshooting.
  • Inverter Compatibility: Designed to work seamlessly with inverter-driven motors.
  • Power Loss Recovery: Ensures reliable operation during power interruptions and restarts.
  • Frequent Start Protection: Safeguards against damage caused by frequent motor starts.

 

Functions of MMP Smart Electronic Motor Protection Relay

Function Range Accuracy(%) Remarks
Voltage (V) 0.00V~9999V ±1.0% Phase1: Phase voltage,
Phase3: Line Voltage
Current (A) 0.00V~9999V ±1.0% Phase current
Zero-phase current (In) 0.00V~9999V ±3.0%
Reverse current (I2) 0.00V~9999V ±3.0%
Active power (W) 0.000W~999.9MW ±1.0% Forward
Reactive power (VAR) 0.000W~999.9MVAR ±1.0% Forward
Active power amount (WH) 0.000W~999.9MWH ±1.0%
Reactive power amount (WVARH) 0.000W~999.9MVARH ±1.0%
PF -1.00~1.00 ±0.03 cosθ
Voltage harmonics (%) 0~100% ±5.0% 2nd -16th odd harmonics
Current harmonics (%) 0~100% ±5.0% 2nd -16th odd harmonics

 

Specification of MMP Smart Electronic Motor Protection Relay

Rating Specification
Communication number 1~247
Baud rate 9600, 19200, 38400 bps
Communication Parity None, Even, Odd
Stop Bit 1bit (fixed)
Communication data swap OFF / ON (Limited to float, long data of 0x04 (Read Input Registers))
Operation mode Differential
Communication distance Max. 1.2km
Cable RS-485 Shielded Twist 2-Pair Cable
Transmission Method Half-Duplex–
Max. In/Output Voltage -7V~+12V