Features of Bender Residual Current Monitor
- Ground-fault monitoring relay with many channels for grounded and high-resistance grounded AC/DC systems
- Observe up to twelve distinct channels, each having a set of customizable alarm trip values.
- On-board menu and real-time readings on a digital display
- Analysis of harmonics and customizable filtering choices
- Connectivity to Ethernet and Modbus communication gateways, as well as contact outputs
- The system has up to 1080 measurement channels and up to 90 RCMS displays.
- Quick parallel channel scanning
- Response ranges are as follows: 100 mA…125 A (42…2000 Hz), 6 mA…20 A (42…2000 Hz), and 10 mA‒10 A (0…2000 Hz). RCMS-D4: Preset feature
- Modifiable time lags
- It is possible to configure the frequency response characteristics for plant, fire, and human safety.
- 300 data records/channel data logger
- Each of the two-alarm relays has one changeover contact.
- Selectable N/O or N/C operation and fault memory
- External test/reset button connection
- Seven-segment backlit graphical display with alarm LEDs
- Data transmission through the BMS bus
- Device settings password protection
- Constant CT connection tracking that complies with RoHS
Applications of Bender Residual Current Monitor
- Monitoring of ground faults in high-resistance grounded AC/DC systems that are grounded
- Systems that use inverters, variable frequency drives, and other power conversion devices
- DC systems for general purposes, as per NEC 250.167(B)
- Distribution of power generally
- Drives and motor management systems
- Systems of control
- The NEC 427.22 and CEC 62-116 guidelines for heat trace systems; the NEC 690.41(B) (2017 edition), NEC 690.5 (2014 edition), and CEC 64-064(4) guidelines for solar arrays
- Systems for storing energy
Specification of Bender Residual Current Monitor
Distinctive device features | RCMS460-D | ||
Parameter setting function | |||
Master/Slave | |||
Address Range | 1…90 | ||
Measuring circuit |
Measuring channels per device | 12 | |
CTAC…, CTUB100, CTBS25, WR…S(P), WS…, W…F series measuring current transformers | |||
CT monitoring | |||
Rated residual operating current I∆n2 (Alarm) |
AC/DC sensitive 0…2000 Hz (Type B) | 10 mA…10 A | |
pulsed DC sensitive 42…2000 Hz (Type A) | 6 mA…20 A | ||
pulsed DC sensitive 42…2000 Hz (Type A) for channels 9…12 (RCMS4x0-D4/-L4) | 100 mA…125 A | ||
Rated residual operating current I∆n1 (prewarning) | 10…100 %, min. 5 mA | ||
Function selectable per channel off, <, >, I/O | |||
Cut-off frequency adjustable for personnel, plant, and fire protection | |||
Preset function for I∆n2 and I/O | |||
Hysteresis | 2…40 % | ||
The factor for additional CT | |||
Switching elements | Common alarm relay for all channels | 2 x 1 changeover contact | |
Alarm relay per channel | – | ||
Time response |
Start-up delay 0…99 s | ||
Response delay TV, adjustable 0…999 s | |||
Operating time at | I∆n = 1 x I∆n2: ≤ 180 ms | ||
I∆n = 5 x I∆n2: ≤ 30ms | |||
Displays, memory |
Analysis of the harmonics (I∆, DC, THF) | ||
History memory 300 data records | |||
Data logger for 300 data records/ channel | |||
Internal clock | |||
Password | |||
Language English, German, French, Swedish | |||
Backlit graphics LC display | |||
7-segment display and LED line | – |