Features of AFR3-06 Arc Detection Device
- Free scaling of the arc protection system
- Various schematic standard solutions:
- Using the central unit
- Without the use of a central unit
- Independence from the RPA system when using the central unit DUGA-BC
- Changing setting groups
- Uniform for all devices software “Configurator-MT” with a graphical logic editor
- Self-diagnosis function that determines the nature of the malfunction
- Extended functionality for recording alarms and events:
- Up to 16000 entries in the event log memory
- Up to 3880 seconds of recording in the oscilloscope memory
- The ability to change the parameters of the recorder and the composition of the signals
- Recorder data deletion protection
- Support for various communication protocols
- Communication interfaces: Ethernet optical, Ethernet RJ-45, serial ports RS-485, USB
- Response time 25..35 ms
Working Principle of AFR3-06 Arc Detection Device
AFR3-06 consists of multiple arc fault recorders for fiber optic sensors and arc fault sensors and one (or more) central unit. The arc fault recorders monitor the equipment’s operating status in real-time and immediately send a signal to the central unit once an arc fault occurs. After receiving the signal, the central unit quickly locates the fault point and issues a command to isolate the faulty equipment, thereby protecting the entire system.
Specification of AFR3-06 Arc Detection Device
Wide temperature range | – 40°С…+55°С |
MTBF | 320,000 hours |
Output relays | 6 pcs |
The angular size of arc control sector | 360 degrees |
Number of arc sensors | 3 pcs |
Maximum sensor length | up to 20 m |
Minimum fixed arc current | 200 A |
Nominal threshold illumination of operation | up to 5,000 Lx |
Warranty | 7 years. Extended warranty option up to 15 years |
Full readiness time when power is turned on | no more than 0.2 s |
Sustained power interruptions | 1 s |