Smart Electronic Motor Protection Relay

Smart Electronic Motor Protection Relay

Contact us
Category:

MMP
Smart Electronic Motor Protection Relay

ㆍCurrent, Voltage, Power Measurement, and Power Factor Protection

ㆍInstantaneous interruption compensation and restarting

ㆍHarmonic measurement (1st to 16th)

ㆍModbus communication and 4~20mA

 

Features

Convenience

ㆍComprehensive digital motor protection relay with the MCU (microprocessor control unit)

ㆍApplicable to inverter circuits

ㆍFunction to store the cause(s) of failure/fault

ㆍOne-body type and separate body type

ㆍCommunication function (RS485 modbus and 4~20ma output)

ㆍA wide range of reset functions

ㆍDate information display

ㆍPassword setting

ㆍTotal operating time and operating time setting

ㆍWide setting of ground fault current sensitivity 30ma~25a

 

Reliability

ㆍThermal heat build-up inverse time/inverse time/definite time selection function

ㆍWide setting range and dual protection

ㆍThe device may be used without external CT up to 100A, providing convenience and cost-effective solution

ㆍVarious motor starting modes

ㆍMetering of current, voltage, and energy (with 1% accuracy for A & V)

ㆍCarries out complex relay functions related to current, voltage, energy, and power factor

ㆍSelf-diagnosis and sequence monitoring

ㆍPower loss and restarting

ㆍFrequent-starting protection

 

Functions

Function Range Accuracy(%) Remarks
Voltage (V) 0.00V~9999V ±1.0% Phase1 : Phase voltage,
Phase3 : Line voltage
Current (A) 0.00V~9999V ±1.0% Phase current
Zero-phase current (In) 0.00V~9999V ±3.0%
Reverse current (I2) 0.00V~9999V ±3.0%
Active power (W) 0.000W~999.9MW ±1.0% Forward
Reactive power (VAR) 0.000W~999.9MVAR ±1.0% Forward
Active power amount (WH) 0.000W~999.9MWH ±1.0%
Reactive power amount (WVARH) 0.000W~999.9MVARH ±1.0%
PF -1.00~1.00 ±0.03 cosθ
Voltage hamonics (%) 0~100% ±5.0% 2nd -16th odd harmonics
Current hamonics (%) 0~100% ±5.0% 2nd -16th odd harmonics

 

Specification

Rating Specification
Communication number 1~247
Baud rate 9600, 19200, 38400 bps
Communication Parity None, Even, Odd
Stop Bit 1bit (fixed)
Communication data swap OFF / ON (Limited to float, long data of 0x04 (Read Input Registers))
Operation mode Differential
Communication distance Max. 1.2km
Cable RS-485 Shielded Twist 2-Pair Cable
Transmission Method Half-Duplex–
Max. In/Output Voltage -7V~+12V