AQ-103LV ARC FLASH PROTECTION DEVICE

AQ-103LV Arc flash protection device is a sophisticated microprocessor-based arc flash protection device for arc light detection. It is designed to minimize the damage caused by an arcing fault (arc flash) by tripping the circuit breaker that sources the fault current. The complete system self-supervision function of AQ-103LV provides the highest level of dependability by continuously monitoring all internal system functions as well as with external connections.

The AQ-103LV arc flash protection device acts as a sub-unit to AQ-110PLV (or, AQ-110FLV) in an AQ 100 arc protection system. It can also function as a stand-alone unit in light-only systems. AQ-103LV provides communication through RS-485 and Modbus protocols as ordering options. Through Modbus communication AQ-103 connects to a local display (AQ-S254A) for indication of exact fault location and to a SCADA system either through an AQ-S254 device or a remote terminal unit (RTU).

Contact us
Category:

Feature:

  • A wide range for the power supply (18…72 V DC or 92…265 V AC/DC).
  • A maximum of 14 arc light point sensors (1 point sensor per channel).
  • A maximum of 1 fiber loop sensor or connection to quenching device (optional).
  • 4 trip relays.
  • 1 system failure relay.
  • 1 fast binary output.
  • 2 fast binary inputs.
  • 1 high-speed output (HSO).
  • 1 multifunction push button.
  • Non-volatile memory.
  • 25 indication LEDs.
  • Modbus protocol (optional).
  • POWER SUPPLY
  • Auxiliary power supply: 92…265 V AC/DC
  • Auxiliary power supply: 18…72 V DC (optional)
  • Maximum interruption: 100 ms
  • Maximum power consumption: 5 W
  • Standby current: 90 mA
  • Light (L>)
  • Light and pressure (L> / P>)
  • Circuit breaker failure protection (50BF/52BF)
  • Total trip time when using mechanical trip relays: 7 ms (only arc light signal from an AQ-110x device)
  • Total trip time when using mechanical trip relays: 7 ms (both overcurrent and arc light signal from an AQ-110x device)
  • Trip time when using solid state trip relays: 2 ms (only arc light signal from an AQ-110x device)
  • Reset time (arc light stage): 2 ms