Medium-voltage cable distribution systems up to 36 kV (± 10%), 50 Hz/60 Hz
Signalization
Fault indication via LEDs
- 1 flag red – earth fault
- 1 LED red – earth fault
- 1 LED yellow – battery charge level when push button is pressed
- 1 LED green – auxiliary voltage available
Binary out- inputs
- 1 binary output for external signal lamp earth fault
- 1 binary output earth fault
- 1 binary output battery monitoring
- 2 binary inputs: 1x AC reset-input, 1x DC reset-input
- 1 binary input remote test / reset
Sensor details
10% accuracy each
- Sensor type 1: earth fault current 25 A to 100 A
for 3 core cable applications
sensor diameter 150 mm
sensor cable length 3.5 m, 5 m
- Sensor type 2: earth fault current 25 A to 240 A
for 3 core cable applications
sensor diameter 140 mm
sensor cable length 16 m
- Sensor type 3: earth fault current 25 A to 240 A
for 3 single core cable applications
flexible sensor diameter 220 mm to 340 mm
sensor cable length 16 m
- Sensor type 4: earth fault current 25 A to 240 A
for 3 core cable applications
sensor diameter 120 mm
sensor cable length 16 m
Auxiliary voltage
- Battery for 2,000 hours flashing time, service life of 15 years min
- 110 – 230 V AC (± 20%)
- 9 – 38 V DC
Temperature range
Housing
- Polycarbonate housing for surface mounting,
optional L-clamp for panel mounting arrangement
- Dimensions: 140 x 150 x 41 mm (W / H / D)
- Protection class: SICAM EFI IP65W, sensor IP68W
- Suitable for detached surface mounting