9000C Series Masibus Signal Isolator

9000C Series Masibus Signal Isolator is compact yet rugged 4 and 2 wire Signal isolators designed for conditioning and safe guarding custom-built wide range of voltage and current  field signals. Field Signal is then isolated and converted to standard instrumentation signals, acceptable to commercially off the shelf (COTS) automation products.

The Aux Powered Model is Equipped with Advanced Extended Power Supply with Supply Range of 20V to 265V AC or DC. 9000C model is further enhanced with Switch selectable I/O configuration for I/O ranges i.e. 0/4-20mA, 0/1-5V and 0-10V. This feature allows user to have freedom to change 0/4-20mA, 0/1-5V and 0-10V I/O types only, using switch available on side of device and with minor tuning using front accessible trim-pots, depending upon field requirements.

Contact us
Category:

Features

  • Available in Aux Powered (AP) and Loop Powered (LP) options
  • Extended Universal Power Supply Range: 20V to 265V DC or AC along with Safe and Sufficient Power For Field 2 Wire Transmitter (Aux Powered Model)
  • Switch Selectable Input/Output option (Aux Powered Model)
  • Rugged & accurate 4 wire and 2 wire isolator
  • Up to 2 outputs with Short Circuit Protection (Aux Powered Model)
  • Wide zero & span adjustment limits
  • 1.5KV AC Isolation between I/P, O/P and Supply
  • High CMRR and NMRR
  • High output Load Driving Capability
  • Lowest Long term Drift

Application

  • Field interface device
  • Transmitter Power Supply
  • Signal Repeater
  • Signal Converter
  • Factory automation
  • Impedance matching of transmitters and receiver instruments

Specifications

Input Type Voltage/Current
 

Input Range

‘L’ Version: 4-20mA

‘S’ Version: 4-20mA (Standard)

‘M’ Version: 0/4 to 20mA , 0/1 to 5V , 0 to 10V (DIP switch selection)

‘H’ Version: 4-20mA, HART Pass

 

Input Impedance

Current Input: ≤100 Ω (Loop Powered)

: ≤10 Ω (Aux Powered) Voltage Input: ≥1 MΩ

CMRR >100 dB
NMRR >70 dB
Temp-co ≤100ppm/°C
Output Type Voltage/Current
Loop Powered ‘L” Version: 4-20mA
 

Aux Powered

‘S’ Version: 4-20mA (Standard)

‘M’ Version: 0/4 to 20mA , 0/1 to 5V , 0 to 10V (DIP switch selection)

‘H’ Version: 4-20mA, HART Pass on o/p-1, 4-20mA, Standard on o/p-2

Response Time ≤50 ms
Accuracy ± 0.1% of FS
Output Load (Loop Powered) RLoad = [(Loop Supply Voltage – 10)/0.021]Ω
 

Output Load (Aux Powered)

mA: ≤750Ω@20mA (SOP),≤550Ω@20mA (DOP)

V: Load Current ≤ 5 mA

(e.g. for 0-5V: 5V/5mA ≥ 1 KΩ)

Output Loop status LED Green (Aux Powered, ‘S’ version only)
TPS Output (Aux Powered) ≈22VDC (±10%) @20mA
Supply (Loop Powered) 10 to 36VDC with reverse polarity protection
Supply (Aux Powered) 20-265V DC/AC (50-60Hz)
Power Consumption (Aux Powered) ≤3W
Power ON status LED Red (Aux Powered only)
Loop Power Model Input to Output: Galvanic Isolation of 1.5KVAC for 1 minute
 

 

 

 

 

 

 

Aux Powered Model

Power to Input and Output :

·    Reinforced insulation according to IEC/EN 61010-1, rated insulation voltage

3KVAC (For CE marked 9000C SOP ‘S’ and ‘M’ Model)

·    Galvanic Isolation of 3KVAC for 1 minute (For CE marked and Non-CE Model)

Input to Output :

·    Functional insulation according to IEC/EN 61010-1, rated insulation voltage

1.5KVAC (For CE marked 9000C SOP ‘S’ and ‘M’ Model)

·    Galvanic Isolation of 1.5KVAC for 1 minute (For CE marked and Non-CE Model)

Output to Output :

·    Galvanic Isolation of 1.5KVAC for 1 minute (For Non-CE Model)

Mounting 35 mm DIN Rail
 

Dimensions in mm

12.5(W)x100.2(H)x115.2(D) mm (For SOP Aux

and Loop Powered Model) 17.5(W)x100.2(H)x115.2(D) mm (For DOP and

HART Pass SOP/DOP)

Enclosure Material PA66
 

Weight

100 gms. Approx for SOP (Aux and Loop Powered)

130 gms. Approx for DOP

Operating temperature 0 to 55 °C
Storage temperature -20 to 85 °C
Humidity 30% to 95% RH(Non-condensing)