Aktif Residual Current Protection Relay

Aktif Residual Current Protection Relay can safeguard your electrical system and prevent accidents. They monitor for earth leakage currents, which can occur due to aging infrastructure, Faulty equipment, and Manufacturing defects.

Earth leakage happens when current escapes the intended path and flows through unintended channels, potentially harming people and equipment.

Aktif Residual Current Protection relay works in conjunction with RCR and ELR series transformers (internal or external) to detect these leaks. They constantly compare the currents entering and exiting a circuit. Any significant difference triggers the relay to instruct the circuit breaker to shut off power, preventing harm.

Contact us

There are ground leakages in the networks due to reasons such as insufficiency of infrastructure, equipment failures, manufacturing faults. RCR and ELR Series Residual Current Protection Relays, which can limit these leakages in a wide range such as 30 mA and 30 A, also have a time setting between 0.02 sec and 5 sec.

The products are used for different purposes depending on their place. While there is a limitation of 25-30 mA in locations with direct human contact, this level is 250-300 mA in locations where fire control is made but there is no human contact. RCR and ELR Series Residual Current Protection Relays can do higher limitations as in both levels.

RCR and ELR Series Residual Current Protection Relays also apply residual current selectivity similar to medium voltage systems. In case of a malfunction, in order for the locations close to the malfunction to be opened first and the main supply not to be cut off; The selectivity can be adjusted with the current limit and tripping times probes on the relay.

Thanks to the test button on the RCR and ELR Series Residual Current Protection Relays, it is possible to control possible residual current relay failures. System refresh is also provided by the reset button.

Features of Aktif Residual Current Protection Relay

  • Flush mounted and DIN rail mounted types
  • Options with low-pass filter unaffacted by harmonics (ELR-3C-F)
  • Type A and Type B (ELR-3A) versions
  • Options with screen (ELR-D2-V) and without screen
  • Real-time monitoring (ELR-D2-V)
  • Configurable pre-alarm indication and fail-safe operation
  • Wide range of sensitivities from 30mA to 3A
  • Delay time setting
  • Versions with RS485 communication (ELR-D2-V, and ELR-4C Series)
  • Versions with 4 completely independent channels (ELR-4C Series)

 

Specification of Aktif Residual Current Protection Relay

FEATURES
ELR-D2-V
ELR-1E/RCR-1p
ELR-3C/RCR-1d
ELR-3C-F
ELRC-1/RCR-T
ELRC-1-F/RCR-T-F
ELRC-B/RCR-Td
TYPE
Type A Type A Type A Type A Type A Type A Type A
TECHNICAL FEATURES
Installation DIN Rail Mounted Panel Mounted DIN Rail Mounted DIN Rail Mounted Compact Compact DIN Rail Mounted
Dimensions 36*90,4*73 96*96 52,5*85*73 52,5*85*73 45*90*74
CONTROL CIRCUIT
Toroidal transformer External External External External Internal
35-60-80-110 mm standard diameter
Internal
35-60-80-110 mm standard diameter
Internal 28mm
Adjustments tripping set-point (I∆) 0.03÷30A 0,025÷25A 0,025÷25A 0,025÷25A 0,025÷25A 0,025÷25A 0,025÷25A
Adjustments tripping time (t) 0,02÷10s 0,02÷5s 0,02÷5s 0,02÷5s 0,02÷5s 0,02÷5s 0,02÷5s
Prealarm set-point 50%…trip set-point
Shunt tripping control 50…90%
AUXILIARY SUPPLY
Auxiliary voltage (US) 110 VAC – 230 VAC 12 VAC/DC
24-48 VAC/DC
110 VAC/DC-240-415 VAC
12 VAC/DC
24-48 VAC/DC
110 VAC/DC-240-415 VAC
12 VAC/DC
24-48 VAC/DC
110 VAC/DC-240-415 VAC
24-48 VAC/DC
110 VAC/DC-240-415 VAC
24-48 VAC/DC
110 VAC/DC-240-415 VAC
24-48 VAC/DC
110 VAC/DC-240-415 VAC
Rated frequency 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz
Maximum power consumption 3 VA 5,5 VA 3 VA 3 VA 3 VA
OUTPUT RELAYS
Contact arrangement 1 changeover (trip) 1 changeover (trip) 1 changeover (trip) 1 changeover (trip) 1 changeover (trip) 1 changeover (trip) 2 changeovers (both trip)
Rated contact capacity Ith 5 A (240 VAC) 5 A (240 VAC) 5 A (240 VAC) 5 A (240 VAC) 5 A (240 VAC) 5 A (240 VAC) 5 A (240 VAC)
INDICATIONS
Auxiliary voltage available (ON) green backlight Green LED Green LED Green LED Green LED Green LED Green LED
Alarm threshold exceeded yellow backlight
Relay tripping (TRIP) red backlight Red LED Red LED Red LED Red LED Red LED Red LED
RS485 SERIAL INTERFACE
Baud-rate Programmable
DISPLAY
Type graphic LCD with RGB backlight
Format 72 x 100 pixel
INSULATION
Insulation test 2.5kV for 1 minute 2.5kV for 1 minute 2.5kV for 1 minute 2.5kV for 1 minute 2.5kV for 1 minute 2.5kV for 1 minute 2.5kV for 1 minute
AMBIENT OPERATING CONDITIONS
Operating temperature -10÷60 °C -10÷60 °C -10÷60 °C -10÷60 °C -10÷60 °C -10÷60 °C -10÷60 °C
Storage temperature -20÷80 °C -20÷80 °C -20÷80 °C -20÷80 °C -20÷80 °C -20÷80 °C -20÷80 °C
Relative humidity  ≤90%  ≤90%  ≤90%  ≤90%  ≤90%  ≤90%  ≤90%
ENCLOSURE
Version 2 modules DIN 96*96 3 modules DIN 3 modules DIN Compact Compact 6 modules DIN
Degree of protection P20 terminals
IP40 with protective cover
P20 terminals
IP40 with protective cover
P20 terminals
IP40 with protective cover
P20 terminals
IP40 with protective cover
P20 terminals
IP40 with protective cover
P20 terminals
IP40 with protective cover
P20 terminals
IP40 with protective cover
OPTIONAL FEATURES
Low Pass Filter (Harmonic Filter)
Built-in filter for 3rd harmonic
CERTIFICATIONS AND COMPLIANCE
Standards IEC/EN 61010, IEC/EN 61000-6-2
IEC/EN 61000-6-3, IEC/TR 60755
CEI EN 60947-2 Ek M
IEC/EN 61010, IEC/EN 61000-6-2
IEC/EN 61000-6-3, IEC/TR 60755
CEI EN 60947-2 Ek M
IEC/EN 61010, IEC/EN 61000-6-2
IEC/EN 61000-6-3, IEC/TR 60755
CEI EN 60947-2 Ek M
IEC/EN 61010, IEC/EN 61000-6-2
IEC/EN 61000-6-3, IEC/TR 60755
CEI EN 60947-2 Ek M
IEC/EN 61010, IEC/EN 61000-6-2
IEC/EN 61000-6-3, IEC/TR 60755
CEI EN 60947-2 Ek M
IEC/EN 61010, IEC/EN 61000-6-2
IEC/EN 61000-6-3, IEC/TR 60755
CEI EN 60947-2 Ek M
IEC/EN 61010, IEC/EN 61000-6-2
IEC/EN 61000-6-3, IEC/TR 60755
CEI EN 60947-2 Ek M
CE