Feature of AQ-M210 electric motor protection devices
- Five (5) thermal models (time constant accurate).
- Soft start protection begins from 6 Hz.
- Wye-delta started motor supervision.
- Two-speed motor protection.
Specification of AQ-M210 electric motor protection devices
Protection | Non-directional overcurrent (I>; 50/51) – 4 stages (INST, DT or IDMT) Non-directional earth fault (I0>; 50N/51N) – 4 stages (INST, DT or IDMT) Negative sequence overcurrent/ Phase current reversal/ Current unbalance (I2>; 46/46R/46L) – 4 stages (INST, DT or IDMT) Harmonic overcurrent (Ih>; 50H/51H/68H) – 4 stages (INST, DT or IDMT) Circuit breaker failure protection (CBFP; 50BF/52BF) High-impedance or low-impedance restricted earth fault/ Cable end differential (I0d>; 87N) Resistance temperature detectors (RTD) Machine thermal overload (TM>; 49M) Motor status monitoring Motor start/ Locked rotor monitoring (Ist>; 48/14) Frequent start (N>; 66) Non-directional undercurrent (I<; 37) Mechanical jam (Im>; 51M) Programmable stage (PGx>/<; 99) Arc protection (IArc>/I0Arc>; 50Arc/50NArc) (optional) |
Control | Number of objects to control and monitor: 5 Number of indicators to monitor: 5 Number of setting groups: 8 Cold load pick-up |
Measuring and Monitoring | Phase, sequence and residual currents (IL1, IL2, IL3, I01, I02) Current transformer supervision Circuit breaker wear monitoring Total harmonic distortion (current) Running hour counter Measurement recorder Measurement value recorder Event recorder (max. 15 000 permanent event records) Disturbance recorder (max. 100 records á 5 seconds at 3.2 kHz sampling) |
Hardware | Current inputs: 5 Digital inputs (fixed): 3 Digital outputs (fixed): 5 Number of empty slots: 4 Digital inputs: +8/16/24/32 (optional) Digital outputs: +5/10 (optional) Milliampere I/O module (4 mA outputs + 1 mA input) Arc protection module (4 sensors + 2 HSO + 1 BI) Communication media (see “Communication” below) External I/O modules (see “Accessories” below) |
Communication Input | RJ-45 100 Mbps Ethernet (front panel, fixed) RJ-45 100 Mbps Ethernet and RS-485 (rear panel, fixed) 2 x RJ-45 100 Mbps Ethernet with an IRIG-B input (optional) 2 x ST 100 Mbps Ethernet with an IRIG-B input (optional) 2 x LC 100 Mbps Ethernet (PRP/HSR) (optional) RS-232 serial fiber (PP/PG/GP/GG) (optional) |
Communication Protocols | IEC 61850 (edition 1) IEC 60870-5-101/104 IEC 60870-5-103 Modbus/RTU and Modbus/TCP DNP3 SPA |