Features
- Full switching of temperature signal
- Using photoelectric isolation technology
- RS485 communication interface
- Relay alarm output
- Low power consumption and low heat generation
- Support transmission output
- Smart appearance and high cost performance
- Transmission accuracy: 0.2%FS (20°C)
- I/O/power isolated from each other
Applications
- Detection, conversion and transmission of temperature in industrial automation control
- In the field of environmental monitoring, the measurement and transmission of atmospheric temperature, water temperature, ground temperature and other parameters are realized
- Used in weather stations, hydrological stations, geological exploration and other fields
- In the field of medical equipment, it realizes the monitoring and transmission of patient body temperature.
- Applied to the cold chain logistics industry to monitor and record the ambient temperature of logistics vehicles and cold storage
Specification
| Input signal | Thermal resistance and thermocouple signal |
| Output signal | 4-20mA, 0-10mA, 0-20mA, 1-5V and 0-5V |
| Output load | 4-20mA, 0-10mA and 0-20mA , load resistanceRL≤500Ω; 1-5V, 0-5V load
resistanceRL≥250KΩ |
| RS485 communication | MODBUS-RTU protocol, RS485 transmission distance≤1,000m, data
transmission rate≤19.2kbps |
| Power | DC/AC20-260V (50/60Hz) |
| Power consumption | Single-input and single-output power consumption: ≤1W, single-input and
double-output and double-input and double-output consumption: ≤1.4W |
| Insulation resistance
(between input/output/power) |
≥100MΩ (500VDC hours) |
| Insulating strength
(between input/output/power) |
1500Vrms (1 min, no spark) |
| Operating temperature | -10~50℃(with no icing or condensation) |
| Relative humidity | 25%~85%RH |
| Storage temperature | -10~60℃(with no icing or condensation) |
| Temperature drift | 0.0075%FS/℃ |
| Installation method | 35mmDIN guide rail installation |
| Installation dimension | 17.5*111.4*121.2mm(W*H*D) |
| Transmission precision (20℃) | 0.2%FS±1 |
| Minimum resolution | 0.1℃ |
| Internal cold junction temperature
compensation range |
-10~50℃ |
| Cold junction compensation
accuracy |
±1℃ |
| Response time | Reach 90% of final value in 50ms |
| Weight | Approximate 140g |
| Electromagnetic compatibility | It should meet industrial equipment application requirements specified in
GB/T18268 (IEC 61326-1) |
| Applicable field equipment | Thermal resistance and thermocouple sensor |