| Subject |
Value |
| Short-circuit Trip Current (Phase to Phase) |
150A, 300A, 450A, 600A, can be set by dial switch during production |
| Trip Current Delay |
40, 80, 120, 200ms, can be set during production |
| Indication Unit Reset |
1. Manual by magnet |
| 2. Time reset: adjustable, 2 minutes, 8h, 24h, 48h, can be set during production |
| 3. Auto reset after repower, 30s default, only for permanent fault |
|
| Protection Class |
IP68 |
| Internal Type Test |
According to IEEE495-2007 |
| Operation |
-40~+70℃ |
| Temperature Range |
| Power Supply |
Lithium battery type AA 3.6V/2.7Ah, replaceable |
| Battery Life |
10 years |
| Weight |
Approx. 600g |
| Dimensions |
Diameter: 93mm |
| Height: 128mm |
| Accuracy |
0A~300A ±3A |
| 300A~800A ±1% |
| Cable Diameter |
6mm~42mm |
| Ranges |
| Blinking Frequency |
10 per minute, adjustable |
| Max. load/fault Current |
1100A |
| Voltage range |
5~14KV. For higher voltage, can be customized |
| Current withstand |
31.5KA/4s |